Skip to main content
Schneider Electric ENW24161 — Air Circuit Breakers

Schneider Electric ENW24161 EasyPact NW Circuit Breaker, 200

MPNENW24161
Active

Schneider Electric EasyPact NW, circuit breaker, ENW24161, 2000 A at 40 °C, 66 kA Icu at 440 V AC, 4P, IP40.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24161 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24161 — Electrical ratings
ParameterValue
Rated current (In)2000 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24161 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH

Performance

ENW24161 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24161 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width537 mm
Height352 mm
Depth297 mm
Neutral pole positionLeft
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24161 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24161 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The ENW24161 is a 4-pole EasyPact NW air circuit breaker rated 2000 A at 40 °C, with a breaking capacity of 66 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC per IEC 60947-2. The 50 kA at 690 V covers industrial 690 V distribution, though the Ics (service breaking capacity) matches the Icu at each voltage level, so it can reclose after a fault without derating. The IP40 enclosure keeps tools and fingers out but is not washdown-rated; mount in a cabinet for wet areas.

Deployment context

Fixed-mount base-plate installation with rear vertical or horizontal connections. The 115 mm connection pitch without spreader matches standard busbar layouts for 2000 A switchgear. Neutral position left, 4P 4d protected poles — covers full four-wire distribution with neutral protection configurable to 0.5 x Ir or 1 x Ir. Mechanical durability of 20,000 cycles with maintenance, 10,000 without; electrical durability of 6,000 cycles at 440 V and 4,000 at 690 V without maintenance — adequate for infrequent switching in distribution, not for frequent motor starting.

Certified to IEC 60947-2, with suitability for isolation marked on the device. The contact position indicator gives visual confirmation of open/closed state — a survey requirement for isolation duty. The breaker's 25 ms maximum breaking time and 70 ms maximum closing response time are typical for air power breakers in this class.

Frequently asked questions

Where can I buy ENW24161 and how do I get a price?

The ENW24161 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What compliance documentation does this brand provide for ENW24161?

The breaker carries IEC 60947-2 certification and is marked for isolation suitability. RoHS and REACH compliance documentation is standard from Schneider Electric for the EasyPact NW series.

MPN
ENW24161