Schneider Electric ENW24168 — Air Circuit Breakers

Schneider Electric ENW24168 EasyPact NW Switch Disconnector,

MPNENW24168
Active

Schneider Electric EasyPact NW, switch disconnector, ENW24168, 3 poles, 1600 A AC-23A, drawout mounting, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ENW24168 — Identification
ParameterValue
Product typeSwitch disconnector
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution
ENW24168 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)AC-23A: 1600 A AC 50/60 Hz 690 V
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3
ENW24168 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)50 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 25 kA during 3 s conforming to IEC 60947-3 at -5...70 °C
Rated short-circuit making capacity (Icm)105 kA AC at 50/60 Hz
ENW24168 — Performance
ParameterValue
Mechanical durability (cycles)20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Utilisation categoryAC-23A
ENW24168 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width441 mm
Height439 mm
Depth395 mm
Connection pitch115 mm without spreader
Connection locationRear
ENW24168 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1
ENW24168 — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

The Schneider Electric ENW24168 is a 3-pole switch disconnector from the EasyPact NW range, rated 1600 A in AC-23A duty at 690 V AC. The 1600 A continuous rating covers high-current distribution or main incomer service in a switchboard. It's designed for isolation per IEC 60947-3, with a visible contact position indicator and a rated impulse withstand voltage of 12 kV.

Short-time withstand current (Icw) is 50 kA for 1 second or 25 kA for 3 seconds at -5 to 70 °C ambient. That's the fault-current the switch can carry without welding or damage during the time it takes an upstream breaker to clear. For coordination studies, the 50 kA / 1 s figure is the one to use for selectivity with a downstream MCCB or fuse. Short-circuit making capacity (Icm) is 105 kA AC — meaning it can close onto a fault and survive. That's relevant if the switch is used as a main disconnect where a fault might already exist when you push it in. The drawout mounting (withdrawn for isolation) and rear vertical/horizontal connection pitch of 115 mm without spreader match standard switchboard busbar layouts.

Drawout mounting on a rail means the switch body can be racked out for maintenance or replacement without disturbing the main bus connections. Rear connection, vertical or horizontal orientation — typical for a fixed-mount switchboard or a withdrawable section. IP40 protection keeps out tools and fingers but not water; install it inside an enclosure rated for the environment.

Frequently asked questions

How do I get current pricing and availability for ENW24168?

Submit an RFQ for the ENW24168. The part is sourced and quoted to order through independent distribution; availability and current pricing are confirmed at quote time.

What is ENW24168's rated operational current?

The ENW24168 is rated 1600 A in AC-23A duty at 690 V AC, 50/60 Hz, per IEC 60947-3.

What compliance documentation does this brand provide for ENW24168?

The ENW24168 is designed and tested to IEC 60947-3, with a rated impulse withstand voltage of 12 kV and pollution degree 4 per IEC 60664-1. It carries a suitability-for-isolation marking. For specific RoHS, REACH, or UL documentation, refer to the manufacturer's compliance declarations available on request.

MPN
ENW24168