Skip to main content
Schneider Electric ENW24168

Schneider Electric ENW24168 EasyPact NW Switch Disconnector,

MPN ENW24168
Active

Schneider Electric EasyPact NW, switch disconnector, ENW24168, 3 poles, 1600 A AC-23A, drawout mounting, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24168 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage690 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 1600 A AC 50/60 Hz 690 V
Utilization categoryAC-23 A
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C

All specifications

ENW24168 additional specifications
ParameterValue
Storage temperature-40...85 °C without control unit
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width441 mm
Height439 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The Schneider Electric ENW24168 is a 3-pole switch disconnector from the EasyPact NW range, rated 1600 A in AC-23A duty at 690 V AC. The 1600 A continuous rating covers high-current distribution or main incomer service in a switchboard. It's designed for isolation per IEC 60947-3, with a visible contact position indicator and a rated impulse withstand voltage of 12 kV.

Short-time withstand current (Icw) is 50 kA for 1 second or 25 kA for 3 seconds at -5 to 70 °C ambient. That's the fault-current the switch can carry without welding or damage during the time it takes an upstream breaker to clear. For coordination studies, the 50 kA / 1 s figure is the one to use for selectivity with a downstream MCCB or fuse. Short-circuit making capacity (Icm) is 105 kA AC — meaning it can close onto a fault and survive. That's relevant if the switch is used as a main disconnect where a fault might already exist when you push it in. The drawout mounting (withdrawn for isolation) and rear vertical/horizontal connection pitch of 115 mm without spreader match standard switchboard busbar layouts.

Drawout mounting on a rail means the switch body can be racked out for maintenance or replacement without disturbing the main bus connections. Rear connection, vertical or horizontal orientation — typical for a fixed-mount switchboard or a withdrawable section. IP40 protection keeps out tools and fingers but not water; install it inside an enclosure rated for the environment.

MPN