Skip to main content
Schneider Electric ENW24174 — Air Circuit Breakers

ENW24174 EasyPact NW Switch Disconnector, 1000A, 3P, Fixed

MPNENW24174
Active

Schneider Electric EasyPact NW, switch disconnector, ENW10N, 1000A AC-23A, 3 poles, fixed mount, rear connection.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

ENW24174 — Identification
ParameterValue
Product typeSwitch disconnector
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution
ENW24174 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)AC-23A: 1000 A AC 50/60 Hz 690 V
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3
ENW24174 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)50 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 25 kA during 3 s conforming to IEC 60947-3 at -5...70 °C
Rated short-circuit making capacity (Icm)105 kA AC at 50/60 Hz
ENW24174 — Performance
ParameterValue
Mechanical durability (cycles)20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Utilisation categoryAC-23A
ENW24174 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width422 mm
Height352 mm
Depth297 mm
Connection pitch115 mm without spreader
Connection locationRear
ENW24174 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1
ENW24174 — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

The Schneider Electric ENW24174 is a fixed-mount switch disconnector from the EasyPact NW range, rated for 1000 A in AC-23A utilisation category at 690 V AC 50/60 Hz. It is a 3-pole device with rear connection, designed for distribution applications where load-break switching and visible isolation are required. The AC-23A rating means it handles occasional switching of motor loads or other highly inductive circuits — not just resistive loads — so it suits mixed-load panels where a general-purpose disconnect is needed rather than a dedicated motor-circuit switch.

Rated operational current (Ie) is 1000 A in AC-23A at 690 V. Rated insulation voltage (Ui) is 1000 V AC, and rated impulse withstand (Uimp) is 12 kV per IEC 60947-3. These tell you the switch is designed for 690 V systems with adequate clearance for surge events up to 12 kV — typical for industrial distribution where the supply transformer and upstream protection set the coordination level. Short-time withstand (Icw) is 50 kA for 1 second or 25 kA for 3 seconds. Short-circuit making capacity (Icm) is 105 kA peak at 50/60 Hz. These numbers define the switch's ability to survive a fault and close onto a short circuit — critical for selectivity studies and SCCR compliance in the panel schedule. Pollution degree 4 per IEC 60664-1 means the switch is rated for harsh environments where conductive pollution (dust, moisture, carbon deposits) is present — typical of heavy industrial or outdoor enclosures.

Fixed mounting on a base plate. Dimensions: 422 mm wide, 352 mm high, 297 mm deep. Connection pitch is 115 mm without spreader. Rear connection position, horizontal or vertical orientation.

Frequently asked questions

Where can I buy ENW24174 and get a price?

The ENW24174 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote.

What is ENW24174's rated operational current?

The rated operational current (Ie) is 1000 A in AC-23A utilisation category at 690 V AC 50/60 Hz.

What compliance standards does ENW24174 meet?

The ENW24174 is designed and tested to IEC 60947-3, with pollution degree 4 per IEC 60664-1. It is suitable for isolation and carries a 12 kV rated impulse withstand voltage.

MPN
ENW24174