Schneider Electric ENW24182 — Air Circuit Breakers

Schneider Electric ENW24182 EasyPact NW Switch Disconnector,

MPNENW24182
Active

Schneider Electric EasyPact NW, switch disconnector, ENW24182, 1000 A AC-23A, 4 poles, drawout, 395 mm depth.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24182 — Identification
ParameterValue
Product typeSwitch disconnector
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24182 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)AC-23A: 1000 A AC 50/60 Hz 690 V
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3

Breaking & withstand capacity

ENW24182 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)50 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 25 kA during 3 s conforming to IEC 60947-3 at -5...70 °C
Rated short-circuit making capacity (Icm)105 kA AC at 50/60 Hz

Performance

ENW24182 — Performance
ParameterValue
Mechanical durability (cycles)20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Utilisation categoryAC-23A

Mechanical & connection

ENW24182 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionLeft
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24182 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24182 — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

The Schneider Electric ENW24182 is a 4-pole switch disconnector from the EasyPact NW range, rated 1000 A in AC-23A utilisation category at 690 V AC. The drawout mounting allows the chassis to be racked out for safe maintenance without disconnecting main power cables, a feature that matters when a line-down event means a freezer starts thawing.

Rated operational current is 1000 A in AC-23A at 690 V. The short-time withstand current (Icw) is 50 kA for 1 s or 25 kA for 3 s, both conforming to IEC 60947-3. This tells you the switch can hold closed through a downstream fault long enough for an upstream breaker to clear, which is the basis for selective coordination in a distribution board. Ambient operating range is -5 to 70 °C, and storage range is -40 to 85 °C, which covers cold storage and freezer anteroom conditions without issue. The switch is certified as suitable for isolation per IEC 60947-3, meaning it provides a visible-break disconnection point for safe maintenance. Rated insulation voltage (Ui) is 1000 V AC, and impulse withstand (Uimp) is 12 kV — this gives headroom for 690 V systems and handles switching surges common in large motor circuits. Electrical durability is 6000 cycles at 440 V and 4000 cycles at 690 V without maintenance; mechanical durability is 20000 cycles with maintenance, 10000 without. For a main disconnect that may be operated once a shift, this is ample; for frequent switching duty, factor in the maintenance interval.

Frequently asked questions

How do I get current pricing and availability for ENW24182?

Submit an RFQ through this listing. The part is sourced to order through independent distribution; availability and current pricing are confirmed at quote time.

What is ENW24182's rated operational current?

The rated operational current (Ie) is 1000 A in AC-23A utilisation category at 690 V AC 50/60 Hz.

What standards does the ENW24182 comply with?

It complies with IEC 60947-3 for switch-disconnectors and IEC 60664-1 for insulation coordination at pollution degree 4.

MPN
ENW24182