Skip to main content
Schneider Electric ENW24193 — Air Circuit Breakers

Schneider Electric ENW24193 EasyPact NW Switch Disconnector,

MPNENW24193
Active

Schneider Electric EasyPact NW, switch disconnector, ENW24193, 2000 A AC-23A, 690 V AC, 4P, fixed mount, IP40.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24193 — Identification
ParameterValue
Product typeSwitch disconnector
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24193 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)AC-23A: 2000 A AC 50/60 Hz 690 V
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3

Breaking & withstand capacity

ENW24193 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)50 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 25 kA during 3 s conforming to IEC 60947-3 at -5...70 °C
Rated short-circuit making capacity (Icm)105 kA AC at 50/60 Hz

Performance

ENW24193 — Performance
ParameterValue
Mechanical durability (cycles)20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Utilisation categoryAC-23A

Mechanical & connection

ENW24193 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width537 mm
Height352 mm
Depth297 mm
Neutral pole positionLeft
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24193 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24193 — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

What this switch disconnector delivers

The Schneider Electric ENW24193 is a 4-pole switch disconnector from the EasyPact NW family, rated for 2000 A in AC-23A duty at 690 V AC — that means it handles heavy motor loads and mixed resistive-inductive circuits common in distribution panels, not just simple resistive switching. The AC-23A utilisation category covers occasional switching of motors, transformers, and capacitor banks, so this part is sized for feeder or main disconnect roles where high inrush currents are expected. Rated short-time withstand current is 50 kA for 1 s (25 kA for 3 s) per IEC 60947-3, and short-circuit making capacity reaches 105 kA AC — selectivity and fault-closure capability are built in for high-fault-level installations.

Fixed mounting on a base plate. Rear connection, vertical or horizontal orientation. Neutral on the left. Connection pitch is 115 mm without spreader. Dimensions: 537 mm wide, 352 mm high, 297 mm deep.

Frequently asked questions

Where can I buy ENW24193 and what is the lead time?

This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here.

What are the key ratings for the ENW24193?

Rated operational current 2000 A in AC-23A at 690 V AC. Short-time withstand current 50 kA for 1 s. Short-circuit making capacity 105 kA AC. Rated impulse withstand voltage 12 kV. Pollution degree 4. IP40 protection.

What compliance documentation does Schneider provide for ENW24193?

The part is designed and tested to IEC 60947-3 for switch-disconnector performance, including isolation suitability. Specific RoHS, REACH, or UL documentation should be requested at RFQ time — the evidence does not list those certificates directly.

MPN