Skip to main content
Schneider Electric ENW24196

Schneider Electric ENW24196 EasyPact NW Switch Disconnector,

MPN ENW24196
Active

Schneider Electric EasyPact NW, switch disconnector, ENW24196, 4000 A AC-23A, 4 poles, fixed mount, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24196 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage690 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 4000 A AC 50/60 Hz 690 V
Utilization categoryAC-23 A
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C

All specifications

ENW24196 additional specifications
ParameterValue
Storage temperature-40...85 °C without control unit
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width537 mm
Height352 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The Schneider Electric ENW24196 is a fixed-mount switch disconnector in the EasyPact NW range, rated 4000 A in AC-23A duty at 690 V AC — that means it handles heavy motor loads and mixed inductive/resistive circuits where the switching frequency is moderate but the fault current potential is high. Four poles, neutral on the left, rear vertical/horizontal connection with a 115 mm pitch without spreader. It's built for distribution panels and main incomer positions where you need a single disconnect that can make and break fault currents up to 121 kA peak and withstand 55 kA for 1 second.

Ratings that matter for the panel designer

The AC-23A utilisation category is the key: it covers switching of motors and other highly inductive loads, and the 4000 A rating at 690 V is the operational current for that duty. Short-time withstand (Icw) is 55 kA for 1 second or 30 kA for 3 seconds — this tells you the disconnector can hold closed under fault current long enough for an upstream breaker to clear, which is critical for selective coordination in a distribution board.

Electrical durability under AC-23A is 5,000 cycles at 440 V and 2,500 cycles at 690 V without maintenance. Ambient operating range is -5 to 70 °C; storage goes from -40 to 85 °C.

Designed and tested to IEC 60947-3 for switch-disconnectors, with a suitability-for-isolation marking. Rated impulse withstand voltage (Uimp) is 12 kV.

MPN
ENW24196