Skip to main content
Schneider Electric ENW24207 — Air Circuit Breakers

ENW24207 EasyPact NW Switch Disconnector, 1250 A, 3P, Fixed

MPNENW24207
Active

Schneider Electric EasyPact NW series, ENW24207 switch disconnector, 1250 A AC-23A, 690 V, 3 poles, fixed mount, IP40.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24207 — Identification
ParameterValue
Product typeSwitch disconnector
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24207 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)AC-23A: 1250 A AC 50/60 Hz 690 V
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3

Breaking & withstand capacity

ENW24207 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)66 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 36 kA during 3 s conforming to IEC 60947-3 at -5...70 °C
Rated short-circuit making capacity (Icm)143 kA AC at 50/60 Hz
Breaking capacity codeHA

Performance

ENW24207 — Performance
ParameterValue
Mechanical durability (cycles)20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Utilisation categoryAC-23A

Mechanical & connection

ENW24207 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width422 mm
Height352 mm
Depth297 mm
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24207 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24207 — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

The ENW24207 is a 3-pole switch disconnector from the EasyPact NW range, rated 1250 A in AC-23A duty at 690 V AC. AC-23A covers switching of motor loads and other highly inductive loads — that 1250 A figure is the current it can make and break under those conditions, not a resistive-heater rating. The 66 kA short-time withstand (1 s) and 143 kA making capacity tell you it holds in under fault until an upstream breaker clears; pollution degree 4 (IEC 60664-1) means it's rated for harsh industrial atmospheres with conductive dust or moisture.

Frequently asked questions

What is ENW24207's rated operational current?

The ENW24207 is rated 1250 A in AC-23A duty at 690 V AC.

What standards does the ENW24207 comply with?

It complies with IEC 60947-3 for switch-disconnectors and is suitable for isolation per that standard.

Where can I buy the ENW24207?

The ENW24207 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

MPN
ENW24207