The Schneider Electric ENW24212 is a fixed-mount switch disconnector from the EasyPact NW range, rated 4000 A in AC-23A utilisation category at 690 V AC. It carries a 66 kA short-time withstand current (Icw) for 1 second and a 143 kA short-circuit making capacity (Icm), which tells you it can survive a bolted fault long enough for upstream protection to clear — important for selectivity coordination in a main feeder position.
Schneider Electric ENW24212 EasyPact NW Switch Disconnector,
MPNENW24212
Active
Schneider Electric EasyPact NW, switch disconnector, ENW24212, 4000 A AC-23A, 3 poles, fixed mount, IP40, 60 kg.
StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
Identification
| Parameter | Value |
|---|---|
| Product type | Switch disconnector |
| Range | EasyPact |
| Product range | EasyPact NW |
| Application | Distribution |
Electrical ratings
| Parameter | Value |
|---|---|
| Rated operational voltage (Ue) | 690 V AC 50/60 Hz conforming to IEC 60947-3 |
| Rated operational current (Ie) | AC-23A: 4000 A AC 50/60 Hz 690 V |
| Poles | 3P |
| Rated insulation voltage (Ui) | 1000 V AC 50/60 Hz conforming to IEC 60947-3 |
| Rated impulse withstand voltage (Uimp) | 12 kV conforming to IEC 60947-3 |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitable for isolation | Yes conforming to IEC 60947-3 |
Breaking & withstand capacity
| Parameter | Value |
|---|---|
| Rated short-time withstand current (Icw) | 66 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 36 kA during 3 s conforming to IEC 60947-3 at -5...70 °C |
| Rated short-circuit making capacity (Icm) | 143 kA AC at 50/60 Hz |
| Breaking capacity code | HA |
Performance
| Parameter | Value |
|---|---|
| Mechanical durability (cycles) | 20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3 |
| Electrical durability (cycles) | AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 |
| Utilisation category | AC-23A |
Mechanical & connection
| Parameter | Value |
|---|---|
| Control type | Push-button |
| Mounting mode | Fixed |
| Mounting support | Base plate |
| Contact position indicator | Yes |
| Width | 422 mm |
| Height | 352 mm |
| Depth | 297 mm |
| Connection pitch | 115 mm without spreader |
| Connection location | Rear |
Environmental
| Parameter | Value |
|---|---|
| Operating ambient temperature | -5...70 °C |
| Storage ambient temperature | -40...85 °C without control unit |
| IP degree of protection | IP40 |
| Pollution degree | 4 conforming to IEC 60664-1 |
Approvals
| Parameter | Value |
|---|---|
| Standards | IEC 60947-3 |
Product details
Frequently asked questions
What are the key ratings of ENW24212?
Rated 4000 A AC-23A at 690 V AC, with a 66 kA short-time withstand current for 1 second and a 143 kA short-circuit making capacity. It is a 3-pole, fixed-mount switch disconnector with IP40 protection, 60 kg weight, and dimensions 422 x 352 x 297 mm.
Where can I buy ENW24212?
ENW24212 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.
MPN
ENW24212
