Skip to main content
Schneider Electric ENW24218

Schneider Electric ENW24218 EasyPact NW Switch Disconnector,

MPN ENW24218
Active

Schneider Electric EasyPact NW series, ENW24218 switch disconnector, 2500 A AC-23A, 4 poles, drawout, H breaking capacity, 395 mm depth.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24218 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage690 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 2500 A AC 50/60 Hz 690 V
Utilization categoryAC-23 A
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C

All specifications

ENW24218 additional specifications
ParameterValue
Storage temperature-40...85 °C without control unit
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width556 mm
Height439 mm
ApplicationDistribution
Operating temperature-5...70 °C

Product details

Switch disconnector, 2500 A, 4 poles — EasyPact NW

The Schneider Electric ENW24218 is a 4-pole switch disconnector from the EasyPact NW range, rated 2500 A in AC-23A utilisation category at 690 V AC. That AC-23A duty covers switching motor loads and other highly inductive circuits — not just resistive heating — so the 2500 A figure is the real motor-switching current, not a derated resistive number. The H breaking capacity code and the 143 kA rated short-circuit making capacity (Icm) tell you this unit can close onto a fault without welding contacts, which matters for distribution incoming or generator coupling where fault levels are high. It's a drawout design on a rail mount, with rear vertical or horizontal connection positions and a 115 mm connection pitch without spreader. The neutral sits on the left. That drawout format means the switching element can be racked out for maintenance or replacement without disturbing the main bus connections — a standard requirement for switchgear where uptime matters.

Withstand and isolation — what the ratings mean

Rated short-time withstand current (Icw) is 66 kA for 1 second or 36 kA for 3 seconds, per IEC 60947-3. That's the current the disconnector can carry without damage during a fault — the 3-second figure is useful for coordination studies where upstream protection has a delayed trip. Rated insulation voltage (Ui) is 1000 V AC, and impulse withstand (Uimp) is 12 kV, so it's comfortable in 690 V systems with typical surge environments. Electrical durability is 5000 cycles at 440 V and 2500 cycles at 690 V without maintenance; mechanical durability is 20000 cycles with maintenance, 10000 without. That's typical for a high-current drawout disconnector — the maintenance interval is the planning point for a PM schedule.

MPN
ENW24218