Skip to main content
Schneider Electric ENW24226 — Air Circuit Breakers

Schneider Electric ENW24226 EasyPact NW Switch Disconnector,

MPNENW24226
Active

Schneider Electric EasyPact NW, switch disconnector, ENW25H, 2500 A AC-23A, 690 V, 4 poles, fixed mount, HA breaking capacity.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24226 — Identification
ParameterValue
Product typeSwitch disconnector
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24226 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)AC-23A: 2500 A AC 50/60 Hz 690 V
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3

Breaking & withstand capacity

ENW24226 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)66 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 36 kA during 3 s conforming to IEC 60947-3 at -5...70 °C
Rated short-circuit making capacity (Icm)143 kA AC at 50/60 Hz
Breaking capacity codeHA

Performance

ENW24226 — Performance
ParameterValue
Mechanical durability (cycles)20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Utilisation categoryAC-23A

Mechanical & connection

ENW24226 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width537 mm
Height352 mm
Depth297 mm
Neutral pole positionLeft
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24226 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24226 — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

The Schneider Electric ENW24226 is a fixed-mount switch disconnector from the EasyPact NW range, rated 2500 A in AC-23A duty at 690 V AC, 50/60 Hz. That AC-23A utilisation category means it is designed for switching motor loads and other highly inductive circuits — not just resistive isolation — and it carries a making capacity of 143 kA peak and a short-time withstand of 66 kA for 1 second per IEC 60947-3. The 4-pole configuration with neutral on the left suits distribution panels where a switched neutral is required, and the rear connection with a 115 mm pitch (without spreader) determines the busbar layout.

The 2500 A continuous rating at 690 V is the headline number, but the AC-23A electrical endurance figures tell the real story for motor-switching applications: 5000 cycles at 440 V without maintenance, dropping to 2500 cycles at 690 V. If your duty cycle exceeds that, you will need to schedule maintenance or upsize. The mechanical durability is 20000 cycles with maintenance, 10000 without — both per IEC 60947-3. The HA breaking capacity code indicates a high interrupting rating, and the rated short-time withstand current of 66 kA for 1 second (36 kA for 3 seconds) gives the selectivity engineer headroom for coordination studies in high-fault-current panels. Pollution degree 4 per IEC 60664-1 is the most severe industrial classification — conductive dust or moisture bridging is expected. This switch disconnector is rated for that environment without derating, which is unusual for a device this size. The IP40 enclosure protection means it is not washdown-rated; it belongs in a clean, dry cabinet. Isolation suitability is confirmed per IEC 60947-3, with a visible contact position indicator. The rated insulation voltage is 1000 V AC, and impulse withstand is 12 kV.

Fixed mounting on a base plate — no DIN rail. The dimensions are 537 mm wide by 352 mm high by 297 mm deep, so the enclosure must accommodate those clearances plus the rear connection depth. The connection pitch of 115 mm without spreader sets the busbar drilling pattern. Horizontal or vertical connection orientation is permitted, giving layout flexibility in the cabinet.

Frequently asked questions

What is the rated operational current of ENW24226?

The rated operational current (Ie) is 2500 A in AC-23A utilisation category at 690 V AC, 50/60 Hz per IEC 60947-3.

What breaking capacity code does ENW24226 carry?

The breaking capacity code is HA, indicating a high interrupting rating. The rated short-time withstand current is 66 kA for 1 second and 36 kA for 3 seconds.

Where can I buy ENW24226 and how is it quoted?

The ENW24226 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quotation.

What standards does ENW24226 comply with?

It complies with IEC 60947-3 for switch-disconnectors, with isolation suitability confirmed. Pollution degree 4 per IEC 60664-1 is also specified.

MPN