Skip to main content
Schneider Electric ENW24229

Schneider Electric ENW24229 EasyPact NW Circuit Breaker, 800

MPN ENW24229
Active

Schneider Electric EasyPact NW, circuit breaker, ENW24229, 800 A, 50 kA Icu at 440 V AC, drawout, 4P, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24229 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C

All specifications

ENW24229 additional specifications
ParameterValue
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width556 mm
Height439 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...60 °C

Product details

The Schneider Electric ENW24229 is an EasyPact NW drawout circuit breaker rated 800 A at 40 °C, with a breaking capacity of 50 kA Icu at 220–440 V AC and 42 kA at 690 V AC per IEC 60947-2. Designed for distribution applications, it provides Category B utilisation with 6000 electrical cycles at 440 V without maintenance. The 4-pole unit mounts on a rail with rear vertical or horizontal connections, and the drawout design simplifies panel maintenance and isolation.

Drawout mounting on a rail with rear connections — vertical or horizontal — means this breaker slides into a cradle without disturbing the bus bars. The 115 mm connection pitch without spreader matches standard EasyPact NW panel cutouts. IP40 enclosure keeps dust out but isn't washdown-rated; install in a clean panel or switchgear cubicle.

Lifecycle status is current.

Rated insulation voltage 1000 V AC, impulse withstand 12 kV.

MPN
ENW24229