Skip to main content
Schneider Electric ENW24231 — Air Circuit Breakers

Schneider Electric ENW24231 EasyPact NW Circuit Breaker, 125

MPNENW24231
Active

Schneider Electric EasyPact NW drawout circuit breaker, ENW24231, 4P, 1250 A at 40 °C, 50 kA Icu at 440 V AC, IEC 60947-2, IP40.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24231 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24231 — Electrical ratings
ParameterValue
Rated current (In)1250 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24231 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN

Performance

ENW24231 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24231 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionRight
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24231 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24231 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The ENW24231 is a 4-pole EasyPact NW drawout circuit breaker rated 1250 A at 40 °C ambient, with a breaking capacity of 50 kA Icu at 220–440 V AC and 42 kA Icu at 690 V AC. The Ics (service breaking capacity) matches the Icu at both voltage levels, so you get full rated performance after clearing a fault — no derating for repeated operation. Pollution degree 4 per IEC 60664-1 means the clearances and creepage distances are designed for harsh environments — conductive dust, condensation, or heavy contamination. This is not a clean-room panel breaker; it belongs in industrial switchrooms where the atmosphere is not controlled.

Lifecycle and compliance — current production, IEC 60947-2

Electrical durability at 440 V is 6,000 cycles without maintenance — typical for a Category B breaker designed for distribution rather than frequent motor switching. The maximum breaking time is 25 ms, closing response 70 ms, which is standard for this class.

Frequently asked questions

What is the breaking capacity of ENW24231 at 690 V?

At 690 V AC the ENW24231 has a breaking capacity of 42 kA Icu and 42 kA Ics, both conforming to IEC 60947-2.

MPN