Schneider Electric ENW24235 — Air Circuit Breakers

Schneider Electric ENW24235 EasyPact NW Circuit Breaker, 320

MPNENW24235
Active

Schneider Electric EasyPact NW drawout circuit breaker, ENW24235, 4-pole, 3200 A rated current at 40 °C, 50 kA Icu at 440 V AC, IEC 60947-2, IP40.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24235 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24235 — Electrical ratings
ParameterValue
Rated current (In)3200 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24235 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN

Performance

ENW24235 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24235 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionRight
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24235 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24235 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric ENW24235 is a 4-pole drawout circuit breaker from the EasyPact NW series, rated 3200 A at 40 °C and designed for distribution applications per IEC 60947-2. The 42 kA Icu at 690 V AC covers the higher-voltage side of the same installation. Category B utilisation means it is certified for selectivity (discrimination) with downstream devices, so a fault on a feeder branch trips only the nearest upstream breaker, not the main — a key requirement for keeping critical processes online during a fault event.

Deployment context: panel integration and environment

Mounts on a rail in a drawout configuration — the breaker chassis slides into a fixed cradle, allowing the power compartment to be isolated for maintenance without unbolting busbars. Rear connection with a 115 mm pitch without spreader mates to standard bus risers in switchgear lineups. Pollution degree 4 per IEC 60664-1 indicates the environment may have conductive dust or heavy condensation — typical of industrial switchrooms near cement, mining, or chemical processing. The neutral position is on the right, which matters when ordering the matching busbar kit.

Frequently asked questions

Who supplies ENW24235 and how is it quoted for volume purchases?

ENW24235 is supplied through independent distribution channels. Volume purchases are quoted against an RFQ — confirm availability and current pricing at quote time.

What is the closest pin-compatible alternative to ENW24235 in this component family?

Within the EasyPact NW series, the device short name ENW32N designates the same 3200 A frame and breaking capacity code N. No pin-compatible alternative outside this series is documented; the ENW24235 order code is the standard offering for this rating.

What is ENW24235's listed depth (395 mm) on this component line?

The ENW24235 has a listed depth of 395 mm, which is the dimension from the front of the breaker to the rear connection plane — relevant for enclosure depth and busbar clearance.

What is ENW24235's listed range (EasyPact) on this component line?

ENW24235 belongs to the EasyPact range, specifically the EasyPact NW series — Schneider Electric's standard offering for air circuit breakers in distribution applications up to 3200 A.

What compliance documentation does this brand provide for ENW24235 (RoHS, REACH, UL, IEC)?

The ENW24235 is certified to IEC 60947-2 and carries a suitability-for-isolation declaration per that standard. The evidence does not list RoHS, REACH, or UL documentation; verify with the supplier at quote stage.

MPN
ENW24235