Skip to main content
Schneider Electric ENW24236

Schneider Electric ENW24236 EasyPact NW Circuit Breaker, 400

MPN ENW24236
Active

Schneider Electric EasyPact NW, circuit breaker, ENW24236, 4000 A, 55 kA Icu at 440 V AC, 4P, drawout, rear connection.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24236 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity55 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C

All specifications

ENW24236 additional specifications
ParameterValue
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width556 mm
Height439 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...60 °C

Product details

What this 4000 A drawout breaker is for

The ENW24236 is a Schneider Electric EasyPact NW circuit breaker rated 4000 A at 40 °C, built for distribution duty in industrial switchgear. It's a 4-pole drawout unit with rear horizontal/vertical connection — the kind of breaker that goes into a main or tie position on a 690 V AC switchboard. The 55 kA Icu at 220...440 V AC (42 kA at 690 V) tells you it handles high fault current without upstream fuses, and the Category B utilisation means it's designed for selectivity with downstream breakers, not just point protection.

The Ics (service breaking capacity) is the same 55 kA at that voltage, meaning it can clear repeated faults at that level and still carry rated current. That's unusual; many breakers derate Ics to 50% or 75% of Icu. Here, Ics = Icu at 440 V, so this unit is built for high-fault installations where you can't afford to lose the main on a downstream short.

Integration into the switchboard

Drawout mounting on rails, rear connection with 115 mm pitch without spreader. The neutral is on the right (fixed position). IP40 enclosure protection keeps tools and fingers out but isn't sealed against water; install in a cabinet rated for the environment. Mechanical durability is 20000 cycles with maintenance, 10000 without — that's a lot of racking operations before the mechanism needs attention.

Certified to IEC 60947-2 for circuit breakers. Rated insulation voltage 1000 V AC, impulse withstand 12 kV. Suitability for isolation is confirmed — the contact position indicator gives visual confirmation of open/closed state, which is what you need for a visible-break isolation point. Storage temperature range -40...85 °C without control unit; operating -5...60 °C. The 25 ms maximum breaking time means fast arc extinction on fault.

MPN
ENW24236