Schneider Electric ENW24243 — Air Circuit Breakers

ENW24243 EasyPact NW Circuit Breaker, 3200 A, 50 kA Icu

MPNENW24243
Active

Schneider Electric EasyPact NW, ENW24243, fixed-mount circuit breaker, 4P, 3200 A at 40 °C, 50 kA Icu at 440 V AC, IEC 60947-2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24243 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24243 — Electrical ratings
ParameterValue
Rated current (In)3200 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24243 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeN

Performance

ENW24243 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24243 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width537 mm
Height352 mm
Depth297 mm
Neutral pole positionRight
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24243 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24243 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

What the 3200 A and 50 kA ratings mean for your main bus

The ENW24243 is a 4-pole EasyPact NW circuit breaker rated 3200 A at 40 °C ambient, meaning it carries that full load continuously through the main distribution bus without derating until the ambient climbs above 40 °C. At 690 V AC the Icu drops to 42 kA, still high enough for most 690 V plant distribution. The Ics (service breaking capacity) matches the Icu at each voltage level, so the breaker clears its maximum fault and remains usable afterward without immediate replacement.

Pollution degree 4 — this breaker lives in the dirt

Pollution degree 4 per IEC 60664-1 means the ENW24243 is rated for conductive pollution environments — think cement plants, foundries, paper mills, or outdoor substations where dust or moisture creates a continuous conductive path. The 12 kV impulse withstand voltage (Uimp) and 1000 V insulation voltage (Ui) back that up: creepage distances are sized to hold off transient overvoltages even when the enclosure is grimy. IP40 on the breaker body keeps out tools and wires larger than 1 mm, but the real protection against conductive contamination comes from the internal insulation coordination, not the housing seal.

Fixed-mount base plate installation, rear-connected. The 537 mm width and 352 mm height fit a standard switchgear cubicle; depth is 297 mm including the operating mechanism. Neutral on the right side of the 4-pole assembly. Connection pitch is 115 mm without a spreader — verify busbar drilling matches before torquing down.

Frequently asked questions

What is the interrupting capacity of ENW24243 at 480 V?

The ENW24243 is rated 50 kA Icu at 220...440 V AC. At 480 V (common in North American 480Y/277 V systems) the Icu is conservatively 50 kA since 480 V falls within the 440 V upper bound of that rating band. For 690 V systems the Icu is 42 kA.

Where can I buy ENW24243 and what is the lead time?

The ENW24243 is sourced to order through independent distribution channels. Submit an RFQ for current availability and pricing; lead time is confirmed at quote time and varies with order quantity and factory backlog.

What compliance documentation does Schneider provide for ENW24243?

The breaker is designed and tested to IEC 60947-2, with suitability for isolation marked on the nameplate. Pollution degree 4 per IEC 60664-1. For specific RoHS, REACH, or UL documentation, request the manufacturer's declaration of compliance with the RFQ.

MPN