Schneider Electric EasyPact NW, drawout circuit breaker, ENW24245, 800 A, 66 kA Icu at 440 V AC, 4P, IP40.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24245 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24245 — Electrical ratings
ParameterValue
Rated current (In)800 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24245 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH

Performance

ENW24245 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24245 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionRight
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24245 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24245 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric ENW24245 is a 4-pole drawout circuit breaker from the EasyPact NW range, rated 800 A at 40 °C and built to IEC 60947-2. It delivers a breaking capacity of 66 kA Icu at 220–440 V AC and 50 kA Icu at 690 V AC, with a corresponding service breaking capacity (Ics) of 65 kA and 50 kA respectively — so it clears faults and stays reusable after a trip at those levels. The 1000 V rated insulation voltage and 12 kV impulse withstand give it headroom for distribution panels feeding motor control centers or step-down transformers.

Deployment context

This is a drawout breaker — mounts on a rail with rear vertical/horizontal connections and a 115 mm pitch without spreader. IP40 enclosure protection suits indoor switchgear, not washdown areas. The push-button control and mechanical contact position indicator make it straightforward for panel builders wiring distribution sections.

Durability and coordination

Rated for 20,000 mechanical cycles with maintenance and 10,000 without; electrical durability is 6,000 cycles at 440 V and 4,000 at 690 V without maintenance. The 25 ms maximum break time and 70 ms closing response support selective coordination downstream.

Listed as current production. No official successor has been issued — this remains the active order code for the 800 A, 66 kA, 4P drawout configuration.

Frequently asked questions

What is the breaking capacity of ENW24245?

66 kA Icu at 220–440 V AC and 50 kA Icu at 690 V AC, per IEC 60947-2. The service breaking capacity (Ics) is 65 kA and 50 kA respectively.

What standards does ENW24245 comply with?

It complies with IEC 60947-2, IEC 60664-1 pollution degree 4, and is suitable for isolation per IEC 60947-2.

Where can I buy ENW24245?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
ENW24245