Schneider Electric ENW24247 — Air Circuit Breakers

Schneider Electric ENW24247 EasyPact NW Circuit Breaker, 125

MPNENW24247
Active

Schneider Electric EasyPact NW, circuit breaker, ENW24247, 1250 A at 40 °C, 66 kA Icu at 220...440 V AC, 4P, drawout, IEC 60947-2.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24247 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24247 — Electrical ratings
ParameterValue
Rated current (In)1250 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24247 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH

Performance

ENW24247 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24247 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionRight
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24247 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24247 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

Its 66 kA Icu at 220...440 V AC (50/60 Hz) per IEC 60947-2 means it can safely interrupt fault currents up to that level without upstream cascading — the sort of rating you need for a main or tie breaker in a low-voltage MCC or switchboard. The drawout mounting lets you rack the breaker out for maintenance or replacement without disturbing the bus connections, which saves hours on a line-down event.

Frequently asked questions

What is the breaking capacity of the ENW24247?

66 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2. The Ics service breaking capacity matches these values.

MPN
ENW24247