Skip to main content
Schneider Electric ENW24253 — Air Circuit Breakers

Schneider Electric ENW24253 EasyPact NW Circuit Breaker, 800

MPNENW24253
Active

Schneider Electric EasyPact NW, circuit breaker, ENW24253, 800 A, 66 kA Icu at 440 V AC, 4P, IP40, fixed mount.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24253 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24253 — Electrical ratings
ParameterValue
Rated current (In)800 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2

Breaking & withstand capacity

ENW24253 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH

Performance

ENW24253 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B

Mechanical & connection

ENW24253 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width537 mm
Height352 mm
Depth297 mm
Neutral pole positionRight
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24253 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24253 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

EasyPact NW ENW24253 — 800 A Air Circuit Breaker

The Schneider Electric ENW24253 is an EasyPact NW air circuit breaker rated 800 A at 40 °C, with a breaking capacity of 66 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2. It is a 4-pole (4P) fixed-mount unit with rear vertical/horizontal connections and a 115 mm connection pitch without spreader. The IP40 enclosure suits indoor distribution panels where dust ingress is limited but not washdown.

At 690 V AC the Icu drops to 50 kA, and the Ics (service breaking capacity) mirrors those values — 65 kA at 440 V, 50 kA at 690 V. The Icw (short-time withstand) is 65 kA for 1 s at 440 V, 36 kA for 3 s at 440/690 V. That 3 s rating matters for selective coordination downstream: the breaker holds closed through a fault long enough for a branch device to clear, avoiding a full panel blackout. Category B utilisation confirms it is designed for selectivity, not just cable protection.

Fixed mounting on a base plate. Rear connection position, vertical or horizontal orientation. The 115 mm connection pitch without spreader matches standard busbar drilling patterns for 800 A class breakers. Neutral is on the right. Pollution degree 4 per IEC 60664-1 means it handles conductive dust and heavy condensation — typical for industrial switchrooms, not clean conditioned spaces.

Electrical Durability and Duty

Mechanical durability: 20,000 cycles with maintenance, 10,000 without. Electrical durability at 440 V AC: 6,000 cycles Category B without maintenance, 4,000 cycles at 690 V. Maximum breaking time 25 ms, maximum closing time 70 ms.

Frequently asked questions

What is the breaking capacity of ENW24253?

66 kA Icu at 220...440 V AC 50/60 Hz, and 50 kA Icu at 690 V AC 50/60 Hz, both per IEC 60947-2. The Ics (service capacity) is 65 kA at 440 V and 50 kA at 690 V.

What is the rated current and voltage for ENW24253?

Rated current (In) is 800 A at 40 °C. Rated operational voltage (Ue) is 690 V AC 50/60 Hz. Rated insulation voltage (Ui) is 1000 V AC.

Where can I buy ENW24253 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures are published here.

What standards does ENW24253 comply with?

IEC 60947-2 (circuit breakers), IEC 60664-1 (pollution degree 4), and it is suitable for isolation per IEC 60947-2. The IP40 rating covers indoor panel use.

MPN