Skip to main content
Schneider Electric ENW24259

Schneider Electric ENW24259 EasyPact NW Circuit Breaker, 320

MPN ENW24259
Active

Schneider Electric EasyPact NW, ENW24259, fixed-mount circuit breaker, 4P, 3200 A, 66 kA Icu at 440 V AC, IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24259 key specifications
ParameterValue
Control typePush-button
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C

All specifications

ENW24259 additional specifications
ParameterValue
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width537 mm
Height352 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...60 °C

Product details

The ENW24259 is a fixed-mount, 4-pole circuit breaker from the EasyPact NW range, rated 3200 A at 40 °C. That current rating places it squarely in main-feed or large-distribution duty — think incoming supply for an industrial switchboard or a high-current bus tie. The 66 kA Icu at 220…440 V AC tells you it can safely interrupt a fault up to that level without rupturing; the 50 kA Icu at 690 V covers higher-voltage installations.

Mounting is fixed to a base plate, with rear connections at a 115 mm pitch without spreader. The footprint is 537 mm wide × 352 mm high × 297 mm deep — plan for a substantial enclosure cut-out and adequate rear-access clearance for cable terminations.

Electrical durability at 440 V is 5,000 cycles without maintenance (Category B, per IEC 60947-2). That's typical for a Category B breaker — designed for distribution, not frequent switching. Maximum breaking time is 25 ms, and the maximum closing response time is 70 ms. The breaker is suitable for isolation, with a visible contact position indicator.

Environmental and insulation

Operating temperature range is -5…60 °C; storage range is -40…85 °C without control unit, -25…85 °C with control unit.

MPN
ENW24259