Skip to main content
Schneider Electric ENW24263 — Air Circuit Breakers

ENW24263 EasyPact NW Switch Disconnector, 1250 A, 4 Poles

MPNENW24263
Active

Schneider Electric EasyPact NW ENW24263, switch disconnector, 1250 A AC-23A, 4 poles, drawout, right neutral, IP40.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24263 — Identification
ParameterValue
Product typeSwitch disconnector
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24263 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)AC-23A: 1250 A AC 50/60 Hz 690 V
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3

Breaking & withstand capacity

ENW24263 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)50 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 25 kA during 3 s conforming to IEC 60947-3 at -5...70 °C
Rated short-circuit making capacity (Icm)105 kA AC at 50/60 Hz

Performance

ENW24263 — Performance
ParameterValue
Mechanical durability (cycles)20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Utilisation categoryAC-23A

Mechanical & connection

ENW24263 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionRight
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24263 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24263 — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

The Schneider Electric ENW24263 is a 4-pole switch disconnector from the EasyPact NW range, rated for 1250 A in AC-23A duty at 690 V AC. The 50 kA rated short-time withstand current (Icw) for 1 second tells you it can ride through a fault long enough for an upstream breaker to clear, which is the kind of coordination a distribution panel needs. It's built for continuous duty, drawout mounting on a rail, with rear vertical or horizontal connection positions. The 395 mm depth and 556 mm width give you the envelope for panel layout — this isn't a compact unit, it's a main breaker-sized disconnector for a switchboard.

The headline number is 1250 A AC-23A at 690 V — that's the motor-switching current, not a resistive-heater rating. The 105 kA making capacity (Icm) means it can close onto a short-circuit without welding contacts, which is critical for a switch that may be called on to energize a faulted bus. That's unusual for a switch disconnector; most stop at PD3. The 12 kV impulse withstand voltage (Uimp) backs this up: it handles surge events common in industrial power systems without flashover. It's suitable for isolation per IEC 60947-3, with a visible contact position indicator. That means a qualified worker can verify the circuit is open by looking at the switch, not relying on a pilot light or meter.

Drawout mounting on a rail means the switch can be racked out for maintenance or replacement without disconnecting the main bus bars — a standard feature for switchboard-grade disconnectors. The right-side neutral position and 115 mm connection pitch without spreader tell you the bus bar layout needs to match this footprint. IP40 protection means it's indoor-only, no washdown. The 6000-cycle electrical durability at 440 V and 4000 cycles at 690 V (AC-23A) gives a realistic service life for a main disconnector — not a daily-operating contactor, but fine for infrequent switching duty.

Frequently asked questions

What is the key rating that decides fit for this switch disconnector?

The 1250 A AC-23A rating at 690 V is the load-switching current for motor circuits. The 50 kA Icw for 1 second tells you the fault-withstand capability for coordination with upstream protection.

Where can I buy ENW24263 and get current pricing?

Sourced and quoted to order against an RFQ through independent industrial distribution. Availability and current pricing are confirmed at quote time.

What standards does ENW24263 comply with?

It complies with IEC 60947-3 for switch-disconnectors, with pollution degree 4 per IEC 60664-1 and a 12 kV impulse withstand voltage.

What is the depth of ENW24263?

The depth is 395 mm, with a width of 556 mm and height of 439 mm. This is a full-size switchboard disconnector, not a panel-mount compact unit.

MPN
ENW24263