Skip to main content
Schneider Electric ENW24265

Schneider Electric ENW24265 EasyPact NW Switch Disconnector,

MPN ENW24265
Active

Schneider Electric EasyPact NW, switch disconnector, ENW24265, 2000 A AC-23A, 4 poles, drawout, 690 V, IEC 60947-3.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24265 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage690 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 2000 A AC 50/60 Hz 690 V
Utilization categoryAC-23 A
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C

All specifications

ENW24265 additional specifications
ParameterValue
Storage temperature-40...85 °C without control unit
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width556 mm
Height439 mm
ApplicationDistribution
Operating temperature-5...70 °C

Product details

Switch disconnector for high-current distribution

The Schneider Electric ENW24265 is a 4-pole switch disconnector from the EasyPact NW range, rated for 2000 A in AC-23A duty at 690 V AC. The drawout mounting lets the unit be racked out for inspection or maintenance without disturbing the rear power connections, which is standard practice for high-current switchgear where access to the main bus is restricted.

Withstand and making capacity — selectivity headroom

Rated short-time withstand current (Icw) is 50 kA for 1 s or 25 kA for 3 s, and the rated short-circuit making capacity (Icm) is 105 kA peak at 50/60 Hz. These figures govern coordination with upstream protective devices: the 50 kA / 1 s rating tells you the switch can carry that fault current long enough for a downstream breaker to clear, so you can achieve selective coordination in a distribution board without the switch failing closed. The 105 kA making capacity means it can close onto an existing fault — a real concern when re-energising a circuit after a fault event.

Dimensions are 556 mm wide × 439 mm high × 395 mm deep. The rear connection location and horizontal/vertical connection orientation mean the bus bars or cables land on the back of the unit, not the front — plan your gland plate and bus run accordingly. Connection pitch is 115 mm without a spreader.

MPN