Skip to main content
Schneider Electric ENW24266

Schneider Electric ENW24266 EasyPact NW Switch Disconnector,

MPN ENW24266
Active

Schneider Electric EasyPact NW switch disconnector, ENW24266, 2500 A AC-23A, 690 V, 4 poles, drawout, right neutral.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24266 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage690 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 2500 A AC 50/60 Hz 690 V
Utilization categoryAC-23 A
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C

All specifications

ENW24266 additional specifications
ParameterValue
Storage temperature-40...85 °C without control unit
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width556 mm
Height439 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The ENW24266 is a Schneider Electric EasyPact NW switch disconnector rated for 2500 A in AC-23A duty at 690 V, 50/60 Hz. With a rated short-time withstand of 50 kA for 1 second and a making capacity of 105 kA, it's sized for high-fault-current distribution panels where isolation and load-break capability are both required. It's a 4-pole drawout unit with the neutral on the right, rear-connected, and mounts on a rail. The drawout construction means the main body can be racked out for maintenance or replacement without disturbing the power wiring — a real time-saver in switchgear that sees regular service.

Where it goes and what it handles

This is a distribution-grade switch disconnector for main or feeder isolation in low-voltage switchboards. The IP40 enclosure rating keeps out tools and fingers but won't stop a hose — it's for indoor, clean-ish environments like a motor control center or a main distribution panel. The 395 mm depth, 556 mm width, and 439 mm height mean it needs a real cubicle — this isn't a DIN-rail breaker. Plan for a dedicated compartment with rear-access cabling and enough swing for the drawout mechanism.

MPN