Skip to main content
Schneider Electric ENW24274

ENW24274 EasyPact NW Switch Disconnector, 2500A, 4P

MPN ENW24274
Active

Schneider Electric EasyPact NW switch disconnector, ENW24274, 2500 A AC-23A, 4 poles, fixed mounting, IP40.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

ENW24274 key specifications
ParameterValue
Control typePush-button
Main product or component typeSwitch disconnector
Voltage690 V AC 50/60 Hz conforming to IEC 60947-3
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-3
CurrentAC-23 A: 2500 A AC 50/60 Hz 690 V
Utilization categoryAC-23 A
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C
Temp operating min-5 °C

All specifications

ENW24274 additional specifications
ParameterValue
Storage temperature-40...85 °C without control unit
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width537 mm
Height352 mm
Mechanical life cycles20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
ApplicationDistribution
Operating temperature-5...70 °C

Product details

What the 2500 A AC-23A rating means for your line

The ENW24274 is a Schneider Electric EasyPact NW switch disconnector rated for 2500 A in AC-23A duty at 690 V AC. AC-23A covers switching of motor loads and other highly inductive loads — this isn't a general-purpose disconnect for resistive heaters; it's sized for the inrush and breaking demands of large motors, transformers, or capacitor banks on a distribution feeder. The 4-pole configuration (right-side neutral) suits it for three-phase plus neutral distribution in panelboards or switchboards where you need a single disconnect point for the entire circuit.

Withstand and making capacity — selectivity headroom

Rated short-time withstand (Icw) is 50 kA for 1 second, or 25 kA for 3 seconds. That's the current the switch can carry without damage during a fault downstream while upstream protective devices clear. The rated short-circuit making capacity (Icm) is 105 kA peak — meaning it can close onto an existing fault without welding contacts. For a site electrical engineer coordinating selectivity, these numbers tell you the switch can sit behind a 50 kA-rated feeder breaker and still maintain coordination downstream.

Fixed mounting on a base plate — no DIN rail for a switch this size. Dimensions are 537 mm wide by 352 mm high by 297 mm deep. Rear connection with vertical or horizontal orientation; connection pitch is 115 mm without spreader. IP40 protection means it's suitable for indoor panel installation where tools are required to access live parts. The isolation suitability per IEC 60947-3 means it provides visible-break isolation — the contact position indicator confirms open/closed status without needing to remove covers.

MPN
ENW24274