Schneider Electric ENW24275 — Air Circuit Breakers

ENW24275 EasyPact NW Switch Disconnector, 3200 A, 4P

MPNENW24275
Active

Schneider Electric EasyPact NW switch disconnector, ENW24275, 3200 A AC-23A, 690 V AC, 4 poles, fixed mounting, IP40.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24275 — Identification
ParameterValue
Product typeSwitch disconnector
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24275 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)AC-23A: 3200 A AC 50/60 Hz 690 V
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3

Breaking & withstand capacity

ENW24275 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)50 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 25 kA during 3 s conforming to IEC 60947-3 at -5...70 °C
Rated short-circuit making capacity (Icm)105 kA AC at 50/60 Hz

Performance

ENW24275 — Performance
ParameterValue
Mechanical durability (cycles)20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Utilisation categoryAC-23A

Mechanical & connection

ENW24275 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width537 mm
Height352 mm
Depth297 mm
Neutral pole positionRight
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24275 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24275 — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

The ENW24275 is a 4-pole switch disconnector from the Schneider Electric EasyPact NW range, rated for 3200 A in AC-23A duty at 690 V AC. It's certified to IEC 60947-3, the standard for switch-disconnectors and load-break switches, and carries a suitability-for-isolation marking, which means it provides visible isolation for safe maintenance access.

Rated short-time withstand current (Icw) is 50 kA for 1 second or 25 kA for 3 seconds — this tells you the switch can hold closed under fault current long enough for an upstream breaker to clear the fault, without welding or failing. The rated short-circuit making capacity (Icm) is 105 kA at AC, meaning it can close onto an existing fault and survive that peak asymmetrical current. Both figures are at the full operating temperature range of -5 to 70 °C. The 4-pole configuration with neutral on the right is fixed — the neutral position is not field-reversible. Connection is rear-mounted, vertical or horizontal orientation, with a 115 mm connection pitch without spreader.

Where this class of part is used

Switch disconnectors of this class serve as the main incoming isolation and load-break device in low-voltage switchboards, motor control centres, and distribution panels. The 3200 A rating places it at the main feeder level for large industrial plants, data centres, or commercial building services where high fault currents and continuous duty are the norm. The continuous duty rating means it's designed to carry rated current indefinitely without derating — not just for occasional switching.

Frequently asked questions

What is ENW24275's rated operational current and voltage?

The ENW24275 is rated 3200 A in AC-23A utilisation category at 690 V AC, 50/60 Hz, certified to IEC 60947-3.