Skip to main content
Schneider Electric ENW24282 — Air Circuit Breakers

Schneider Electric ENW24282 EasyPact NW Switch Disconnector,

MPNENW24282
Active

Schneider Electric EasyPact NW, switch disconnector, ENW25H, 2500 A AC-23A, 4 poles, drawout, right neutral, IP40.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24282 — Identification
ParameterValue
Product typeSwitch disconnector
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24282 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)AC-23A: 2500 A AC 50/60 Hz 690 V
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3

Breaking & withstand capacity

ENW24282 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)66 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 36 kA during 3 s conforming to IEC 60947-3 at -5...70 °C
Rated short-circuit making capacity (Icm)143 kA AC at 50/60 Hz
Breaking capacity codeHA

Performance

ENW24282 — Performance
ParameterValue
Mechanical durability (cycles)20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Utilisation categoryAC-23A

Mechanical & connection

ENW24282 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeDrawout
Mounting supportRail
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionRight
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24282 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24282 — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

The Schneider Electric ENW24282 is a 4-pole switch disconnector from the EasyPact NW series, rated for 2500 A in AC-23A duty at 690 V AC. The drawout mounting (withdrawal chassis) lets you rack the unit out for inspection or replacement without disturbing the main bus connections — a real time-saver on switchgear where panel access is tight. Connection is rear-mounted, horizontal or vertical, with a 115 mm pitch without spreader.

The AC-23A utilisation category covers switching of motor loads and other highly inductive circuits — 2500 A at 690 V is the operational current for that duty. For short-circuit conditions, the rated short-time withstand current (Icw) is 66 kA for 1 s and 36 kA for 3 s, and the making capacity (Icm) hits 143 kA peak. Those numbers tell you this disconnector can hold closed through a fault long enough for an upstream breaker to clear, without welding contacts. The IP40 enclosure keeps out tools and small solids but not moisture; if washdown is in the picture, plan for a higher-rated enclosure around it. Electrical durability under AC-23A is 5000 cycles at 440 V and 2500 cycles at 690 V — this is not a part you cycle daily in a high-speed process; it is a service disconnect that sees tens of operations per year.

Frequently asked questions

Where can I buy ENW24282 and how do I get a price?

The ENW24282 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What are the key ratings for ENW24282?

The ENW24282 is rated 2500 A operational current in AC-23A duty at 690 V AC, with a short-time withstand current of 66 kA for 1 s and a making capacity of 143 kA peak. It is a 4-pole switch disconnector with drawout mounting, suitable for isolation per IEC 60947-3.

What compliance documentation does Schneider provide for ENW24282?

The ENW24282 is designed and tested to IEC 60947-3, with a rated insulation voltage of 1000 V AC and impulse withstand voltage of 12 kV. Pollution degree 4 per IEC 60664-1 is declared. For specific RoHS/REACH/UL documentation, request the manufacturer's compliance declaration at quote time.

MPN