The ENW24285: Rated operational current of 800 A in AC-23A at 690 V — that's the motor-switching category per IEC 60947-3, so it's rated for the high inrush of starting motors and the arc that follows. The rated short-time withstand current (Icw) of 66 kA for 1 second means the switch can hold its contacts closed under fault current long enough for an upstream breaker to clear the fault — critical for selectivity coordination in a distribution panel. Rated impulse withstand voltage of 12 kV covers surge environments typical of industrial mains. The IP40 enclosure protection means it's not for washdown areas, but fine for a clean indoor switchboard.
Fixed mounting on a base plate, rear connection. Footprint: 537 mm wide, 352 mm high, 297 mm deep. Connection pitch is 115 mm without spreader — that's the busbar spacing you need to plan for in the switchboard layout. Right-side neutral position means the neutral bar lands on the right when facing the switch. Vertical or horizontal connection orientation accepted.