Skip to main content
Schneider Electric ENW24286 — Air Circuit Breakers

Schneider Electric ENW24286 EasyPact NW Switch Disconnector,

MPNENW24286
Active

Schneider Electric EasyPact NW series, ENW24286 switch disconnector, 1000 A rated operational current, AC-23A, 4 poles, right neutral, fixed mounting, 537 x 352 x 297 mm.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24286 — Identification
ParameterValue
Product typeSwitch disconnector
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24286 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)AC-23A: 1000 A AC 50/60 Hz 690 V
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3

Breaking & withstand capacity

ENW24286 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)66 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 36 kA during 3 s conforming to IEC 60947-3 at -5...70 °C
Rated short-circuit making capacity (Icm)143 kA AC at 50/60 Hz
Breaking capacity codeHA

Performance

ENW24286 — Performance
ParameterValue
Mechanical durability (cycles)20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Utilisation categoryAC-23A

Mechanical & connection

ENW24286 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width537 mm
Height352 mm
Depth297 mm
Neutral pole positionRight
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24286 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24286 — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

The ENW24286 is a 4-pole switch disconnector in the Schneider Electric EasyPact NW range, rated for distribution duty. It carries a 1000 A rated operational current (Ie) in AC-23A utilisation category at 690 V AC 50/60 Hz — that's the heavy switching category for motor loads, inductive and resistive mixed, where making and breaking currents are high. Rated insulation voltage (Ui) is 1000 V AC, and impulse withstand (Uimp) is 12 kV, both per IEC 60947-3.

Short-circuit and isolation performance

Rated short-time withstand current (Icw) is 66 kA for 1 s or 36 kA for 3 s, and short-circuit making capacity (Icm) hits 143 kA peak at 50/60 Hz. These numbers govern selectivity coordination downstream — the disconnector holds in during a fault long enough for the downstream breaker to clear, without welding its own contacts. It's certified as suitable for isolation per IEC 60947-3, with a visible contact position indicator. That means it can serve as a lockable disconnect point for safe maintenance access — no separate isolator needed upstream.

Fixed mounting on a base plate, rear connection, right-side neutral position. The 537 x 352 x 297 mm footprint needs panel layout planning — it's not a DIN-rail part. Connection pitch is 115 mm without spreader; vertical or horizontal cable entry works. IP40 enclosure protection — suitable for indoor panel installation, not washdown.

Frequently asked questions

Where can I buy ENW24286 and how do I get a price?

The ENW24286 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is ENW24286's rated operational current and utilisation category?

The ENW24286 is rated 1000 A in AC-23A utilisation category at 690 V AC 50/60 Hz, per IEC 60947-3.

What compliance documentation does this brand provide for ENW24286?

The ENW24286 is certified to IEC 60947-3 and IEC 60664-1 (pollution degree 4). The manufacturer provides standard compliance documentation for these standards.

MPN