Skip to main content
Schneider Electric ENW24289 — Air Circuit Breakers

ENW24289 EasyPact NW Switch Disconnector, 2000A, 4P, Right

MPNENW24289
Active

Schneider Electric EasyPact NW, switch disconnector, ENW24289, 2000 A AC-23A, 690 V, 4 poles, right neutral, fixed mounting, IP40.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

ENW24289 — Identification
ParameterValue
Product typeSwitch disconnector
RangeEasyPact
Product rangeEasyPact NW
ApplicationDistribution

Electrical ratings

ENW24289 — Electrical ratings
ParameterValue
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-3
Rated operational current (Ie)AC-23A: 2000 A AC 50/60 Hz 690 V
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-3
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-3
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-3

Breaking & withstand capacity

ENW24289 — Breaking & withstand capacity
ParameterValue
Rated short-time withstand current (Icw)66 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 36 kA during 3 s conforming to IEC 60947-3 at -5...70 °C
Rated short-circuit making capacity (Icm)143 kA AC at 50/60 Hz
Breaking capacity codeHA

Performance

ENW24289 — Performance
ParameterValue
Mechanical durability (cycles)20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3
Electrical durability (cycles)AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3
Utilisation categoryAC-23A

Mechanical & connection

ENW24289 — Mechanical & connection
ParameterValue
Control typePush-button
Mounting modeFixed
Mounting supportBase plate
Contact position indicatorYes
Width537 mm
Height352 mm
Depth297 mm
Neutral pole positionRight
Connection pitch115 mm without spreader
Connection locationRear

Environmental

ENW24289 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1

Approvals

ENW24289 — Approvals
ParameterValue
StandardsIEC 60947-3

Product details

The ENW24289 is a 4-pole switch disconnector from the EasyPact NW range, rated for distribution duty and built to IEC 60947-3. It is certified for isolation (suitability for isolation conforming to IEC 60947-3), so it can safely disconnect a circuit for maintenance or emergency stop. Its headline rating is 2000 A in AC-23A utilisation category at 690 V AC 50/60 Hz — that means it handles the high inrush of motor or inductive loads on switching, not just resistive. AC-23A is the heavy-duty motor-switching class; the 2000 A figure is the operational current at that duty. The switch is fixed-mounted on a base plate, with rear horizontal/vertical connection positions and a right-side neutral. The 115 mm connection pitch without spreader sets the busbar layout.

Rated short-time withstand current (Icw) is 66 kA for 1 s or 36 kA for 3 s — this tells you the switch can survive a fault current of that magnitude long enough for an upstream breaker to clear. The rated short-circuit making capacity (Icm) is 143 kA peak at 50/60 Hz, which is the peak current it can close into without welding contacts. IP40 protection means the enclosure keeps out tools and wires over 1 mm but is not sealed against water — suitable for indoor panel installation, not washdown areas.

Frequently asked questions

How do I get current pricing and availability for ENW24289?

Submit an RFQ through the storefront. Availability and current pricing are confirmed at quote time — no stock or price figures are published here.

What is ENW24289's rated operational current?

2000 A in AC-23A utilisation category at 690 V AC 50/60 Hz. That is the current for motor-switching duty, not resistive load.

What standards does the ENW24289 comply with?

It complies with IEC 60947-3 for switch-disconnectors and IEC 60664-1 for pollution degree 4. It is certified for isolation per IEC 60947-3.

MPN