Skip to main content
Schneider Electric EVS08H4MW6A — Air Circuit Breakers

Schneider Electric EVS08H4MW6A EasyPact EVS Circuit Breaker,

MPNEVS08H4MW6A
Active

Schneider Electric EasyPact EVS EVS08H4MW6A, drawout circuit breaker, 4P, 800 A, 65 kA Icu at 440 V AC, electronic trip unit EVS Trip System6A, IP40.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EVS08H4MW6A — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact EVS
ApplicationDistribution
EVS08H4MW6A — Electrical ratings
ParameterValue
Rated current (In)800 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles4P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
EVS08H4MW6A — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
EVS08H4MW6A — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
EVS08H4MW6A — Mechanical & connection
ParameterValue
Control typeManually operated
Mounting modeDrawout
Mounting supportRail Base plate
Contact position indicatorYes
Width556 mm
Height439 mm
Depth395 mm
Neutral pole positionLeft
Connection pitch115 mm without spreader
Connection locationRear
EVS08H4MW6A — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1
EVS08H4MW6A — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric EasyPact EVS08H4MW6A is a 4-pole drawout circuit breaker rated 800 A at 40 °C, with an electronic trip unit (EVS Trip System6A) that covers overload (long-time), instantaneous short-circuit, short-time short-circuit, and earth-fault protection. Its 65 kA Icu at 220...440 V AC (50/60 Hz) per IEC 60947-2 means it can safely interrupt fault currents up to that level without upstream cascading — critical for high-fault-capacity distribution panels. Category B utilisation means it is designed for selectivity with downstream devices, not just cable protection. The drawout mounting and rear connection suit switchgear assemblies where the breaker must be racked out for maintenance without de-energising the bus. The digital display on the trip unit gives local readout of fault type (internal fault, overload, short-circuit, earth fault) and thermal memory status — the 20-minute thermal memory before and after tripping means the breaker remembers its thermal state even after a trip, preventing immediate reclose on a still-hot conductor.

The EVS08H4MW6A is listed as current-production (lifecycle stage: current). No official successor has been assigned — this is the active variant in the EasyPact EVS range.

Mounts on a rail or base plate in a drawout configuration — typical for metal-enclosed low-voltage switchgear (MCC or distribution board). The 556 mm width, 439 mm height, and 395 mm depth define the cell cutout; connection pitch is 115 mm without spreader. Neutral is on the left. Vertical or horizontal connection positions allow top-feed or bottom-feed bus arrangements.

MPN
EVS08H4MW6A