Schneider Electric EVS10H3MF20 EasyPact EVS Circuit Breaker,

MPN EVS10H3MF20
Active

Schneider Electric EasyPact EVS, circuit breaker, EVS10H3MF20, 3P, 1000 A at 40 °C, 65 kA Icu at 440 V AC, EVS Trip System2.0, IEC 60947-2.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EVS10H3MF20 key specifications
ParameterValue
Control typeManually operated
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C

All specifications

EVS10H3MF20 additional specifications
ParameterValue
Temp operating min-5 °C
Pollution degree4 conforming to IEC 60664-1
Depth297 mm
Width422 mm
Height352 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...70 °C

Product details

What this 1000 A breaker is for

The Schneider Electric EVS10H3MF20 is a 3-pole EasyPact EVS circuit breaker with a 1000 A trip unit rating and a 65 kA Icu breaking capacity at 440 V AC. It's built for distribution duty in fixed-mount switchboards, manually operated, with an electronic trip unit (EVS Trip System2.0) that provides overload and instantaneous short-circuit protection.

Rated current is 1000 A at 40 °C ambient — that's the continuous load it carries without derating. Above 40 °C, the electronic trip unit's thermal memory (20 min reset time) tracks the heating curve, so a hot breaker won't nuisance-trip on a restart. For a 480 V distribution panel, that's still well above typical utility transformer secondary fault levels.

Fixed-mount design — bolts to a base plate or rail base. Connection pitch is 115 mm without a spreader; rear-connected vertical or horizontal bus bars. Dimensions: 422 mm wide × 352 mm high × 297 mm deep. The mechanical interlock and contact position indicator are standard, so you can wire a status feedback to the PLC without extra aux contacts.

MPN
EVS10H3MF20