The EVS10H3MW5A is a 3-pole drawout circuit breaker from the Schneider Electric EasyPact EVS range, rated 1000 A at 40 °C and built to IEC 60947-2. The 65 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC define the maximum fault current it can safely interrupt — critical for coordination studies on distribution switchboards where the available fault current exceeds 50 kA. The electronic trip unit (EVS Trip System5A) provides overload (long-time), short-time, and instantaneous short-circuit protection, with a 20-minute thermal memory that retains heating history before and after a trip event. This matters for motor or transformer feeders where repeated overloads close together would otherwise cause nuisance tripping. Drawout mounting means the breaker chassis stays wired to the bus; the moving portion withdraws for maintenance or replacement without disturbing the primary connections. The rear connection position with a 115 mm pitch without spreader matches standard switchboard busbar spacing — verify the existing busbar centers before specifying.
Schneider Electric EVS10H3MW5A EasyPact EVS Circuit Breaker,
Schneider Electric EasyPact EVS, drawout circuit breaker, EVS10H3MW5A, 3P, 1000 A, 65 kA Icu at 440 V AC, electronic trip unit.
Specifications
| Parameter | Value |
|---|---|
| Product type | Circuit breaker |
| Range | EasyPact |
| Product range | EasyPact EVS |
| Application | Distribution |
| Parameter | Value |
|---|---|
| Rated current (In) | 1000 A at 40 °C |
| Rated operational voltage (Ue) | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Poles | 3P |
| Rated insulation voltage (Ui) | 1000 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated impulse withstand voltage (Uimp) | 12 kV conforming to IEC 60947-2 |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitable for isolation | Yes conforming to IEC 60947-2 |
| Parameter | Value |
|---|---|
| Rated service breaking capacity (Ics) | 65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated short-time withstand current (Icw) | 65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated short-circuit making capacity (Icm) | 143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity | 65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code | H |
| Parameter | Value |
|---|---|
| Breaking time, max. | 25 ms |
| Closing response time, max. | 70 ms |
| Mechanical durability (cycles) | 20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2 |
| Electrical durability (cycles) | Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 |
| Utilisation category | Category B |
| Parameter | Value |
|---|---|
| Control type | Manually operated |
| Mounting mode | Drawout |
| Mounting support | Rail Base plate |
| Contact position indicator | Yes |
| Width | 441 mm |
| Height | 439 mm |
| Depth | 395 mm |
| Connection pitch | 115 mm without spreader |
| Connection location | Rear |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -5...70 °C |
| Storage ambient temperature | -40...85 °C without control unit -25...85 °C with control unit |
| IP degree of protection | IP40 |
| Pollution degree | 4 conforming to IEC 60664-1 |
| Parameter | Value |
|---|---|
| Standards | IEC 60947-2 |
Product details
Frequently asked questions
Where can I buy EVS10H3MW5A and how do I get a price?
The EVS10H3MW5A is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.
What is the breaking capacity of EVS10H3MW5A?
The EVS10H3MW5A has a breaking capacity of 65 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2.
What compliance documentation does Schneider Electric provide for EVS10H3MW5A?
The EVS10H3MW5A is certified to IEC 60947-2 and carries suitability for isolation per that standard. For specific RoHS, REACH, or UL documentation, request the compliance package at quote time.