The Schneider Electric EVS10H3NW5A is a 3-pole EasyPact EVS drawout circuit breaker rated 1000 A at 40 °C, with an electronic trip unit (EVS Trip System5A) providing overload, short-time, and instantaneous short-circuit protection. Its 65 kA Icu at 440 V AC (50/60 Hz) per IEC 60947-2 gives you headroom for high-fault distribution panels — the H breaking capacity code means it handles the heavy side of the switchboard without cascading upstream.
Protection and coordination details
Pollution degree 4 per IEC 60664-1 means the breaker is rated for harsh, conductive environments (dust, condensation) typical of heavy industrial switchrooms. Suitability for isolation per IEC 60947-2 and a mechanical durability of 20,000 cycles with maintenance make it a candidate for main incomer or feeder duty where long service life and safe isolation are required.