Skip to main content
Schneider Electric EVS16H3MF20 — Air Circuit Breakers

Schneider Electric EVS16H3MF20 EasyPact EVS Circuit Breaker,

MPNEVS16H3MF20
Active

Schneider Electric EasyPact EVS, EVS16H3MF20, 3-pole circuit breaker, 1600 A rated current, 65 kA breaking capacity at 440 V AC, electronic trip unit.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EVS16H3MF20 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact EVS
ApplicationDistribution
EVS16H3MF20 — Electrical ratings
ParameterValue
Rated current (In)1600 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
EVS16H3MF20 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
EVS16H3MF20 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
EVS16H3MF20 — Mechanical & connection
ParameterValue
Control typeManually operated
Mounting modeFixed
Mounting supportRail Base plate
Contact position indicatorYes
Width422 mm
Height352 mm
Depth297 mm
Connection pitch115 mm without spreader
Connection locationRear
EVS16H3MF20 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1
EVS16H3MF20 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric EVS16H3MF20 is a 3-pole EasyPact EVS circuit breaker with a 1600 A rated current (In) at 40 °C and a 65 kA Icu breaking capacity at 220...440 V AC 50/60 Hz per IEC 60947-2. The electronic EVS Trip System2.0 provides LI protection (long-time overload and instantaneous short-circuit) with a 20-minute thermal memory before and after tripping, which means it remembers the heat profile of a prior overload and won't reclose into a still-hot conductor. This is a Category B circuit breaker (IEC 60947-2), meaning it's designed for distribution duty with intentional short-time delay coordination — not just cable protection. Pollution degree 4 per IEC 60664-1 means it's rated for continuous conductive contamination (condensation, heavy dust), so it belongs in an enclosure that keeps the environment at IP40 or better — the breaker itself carries IP40.

Fixed-mount design, rear-connected, with a 115 mm connection pitch without spreader. Mounts on a rail or base plate — the 422 mm width and 352 mm height fit a standard switchboard cubicle. Vertical or horizontal connection orientation gives you flexibility in busbar layout. The manually operated control type means no motor operator is integrated; if remote closing is needed, plan for an external operator accessory.

Electrical durability at 440/690 V AC is 5,000 cycles (Category B, no maintenance) per IEC 60947-2. Maximum breaking time is 25 ms, maximum closing response time 70 ms — fast enough for most coordination schemes but check your upstream device's let-through curve if you're running a fully selective system.

Frequently asked questions

What is the breaking capacity of EVS16H3MF20?

65 kA Icu at 220...440 V AC 50/60 Hz and 50 kA Icu at 690 V AC 50/60 Hz, both conforming to IEC 60947-2.

What trip unit does EVS16H3MF20 use?

It uses the EVS Trip System2.0 electronic trip unit with LI protection — long-time overload and instantaneous short-circuit protection.

Where can I buy EVS16H3MF20?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

MPN
EVS16H3MF20