Skip to main content
Schneider Electric EVS16H3MW60

Schneider EVS16H3MW60 EasyPact Circuit Breaker, 1600 A, 65 k

MPN EVS16H3MW60
Active

Schneider Electric EasyPact EVS, drawout circuit breaker, EVS16H3MW60, 1600 A, 65 kA Icu at 440 V AC, 3-pole, electronic trip unit EVS Trip System6.0.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EVS16H3MW60 key specifications
ParameterValue
Control typeManually operated
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max70 °C

All specifications

EVS16H3MW60 additional specifications
ParameterValue
Temp operating min-5 °C
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width441 mm
Height439 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...70 °C

Product details

What this 1600 A drawout breaker does on the line

The Schneider Electric EVS16H3MW60 is a 1600 A drawout circuit breaker from the EasyPact EVS range, built for distribution duty in industrial switchgear. It carries a 65 kA Icu at 220…440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2 — enough to handle high-fault utility feeds without cascading upstream. The electronic EVS Trip System6.0 unit gives you overload (long-time), instantaneous short-circuit, short-time short-circuit, and earth-fault protection, all adjustable.

Mounting and panel fit — drawout frame, rear connection

Drawout mounting means the breaker slides into a cradle on a rail or base plate — no hard wiring to the breaker body, so swap-out is a racking handle and a few minutes. Rear vertical or horizontal connection at 115 mm pitch without spreader. Dimensions: 441 mm wide, 439 mm tall, 395 mm deep. IP40 on the front, pollution degree 4 per IEC 60664-1 for harsh environments. Contact position indicator is visible through the door.

Durability and duty cycle — Category B, 5000 electrical cycles

Electrical durability: 5000 cycles at 440/690 V AC without maintenance. Mechanical: 20,000 cycles with maintenance, 10,000 without. Maximum breaking time 25 ms, maximum closing time 70 ms. Suitability for isolation is marked yes per the same standard.

MPN
EVS16H3MW60