The EVS20H3MW60 is a Schneider Electric EasyPact EVS drawout circuit breaker rated 2000 A at 40 °C, with a breaking capacity of 65 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2.
Fitted with the EVS Trip System6.0 electronic trip unit, it provides overload (long-time), instantaneous short-circuit, short-time short-circuit, and earth-fault protection.
Electrical and mechanical endurance
Rated for 5000 electrical cycles at 440/690 V AC without maintenance (Category B per IEC 60947-2). Mechanical durability is 20000 cycles with maintenance, 10000 without. The 25 ms maximum breaking time means fast fault clearance — important for arc-flash energy reduction.
Drawout mounting on a rail or base plate. Rear connection, vertical or horizontal orientation. IP40 protection — suitable for clean indoor switchgear, not washdown areas. Pollution degree 4 per IEC 60664-1, meaning it handles conductive pollution environments (typical for industrial switchboards).