Schneider Electric EVS20H3MW60 — Air Circuit Breakers

Schneider Electric EVS20H3MW60 EasyPact EVS Circuit Breaker,

MPNEVS20H3MW60
Active

Schneider Electric EasyPact EVS, drawout circuit breaker, 3P, 2000 A rated current, 65 kA Icu at 440 V AC, IEC 60947-2, electronic trip unit EVS Trip System6.0.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EVS20H3MW60 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact EVS
ApplicationDistribution
EVS20H3MW60 — Electrical ratings
ParameterValue
Rated current (In)2000 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
EVS20H3MW60 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
EVS20H3MW60 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
EVS20H3MW60 — Mechanical & connection
ParameterValue
Control typeManually operated
Mounting modeDrawout
Mounting supportRail Base plate
Contact position indicatorYes
Width441 mm
Height439 mm
Depth395 mm
Connection pitch115 mm without spreader
Connection locationRear
EVS20H3MW60 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1
EVS20H3MW60 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The EVS20H3MW60 is a Schneider Electric EasyPact EVS drawout circuit breaker rated 2000 A at 40 °C, with a breaking capacity of 65 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2.

Fitted with the EVS Trip System6.0 electronic trip unit, it provides overload (long-time), instantaneous short-circuit, short-time short-circuit, and earth-fault protection.

Electrical and mechanical endurance

Rated for 5000 electrical cycles at 440/690 V AC without maintenance (Category B per IEC 60947-2). Mechanical durability is 20000 cycles with maintenance, 10000 without. The 25 ms maximum breaking time means fast fault clearance — important for arc-flash energy reduction.

Drawout mounting on a rail or base plate. Rear connection, vertical or horizontal orientation. IP40 protection — suitable for clean indoor switchgear, not washdown areas. Pollution degree 4 per IEC 60664-1, meaning it handles conductive pollution environments (typical for industrial switchboards).

Frequently asked questions

What is the breaking capacity of EVS20H3MW60?

65 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2.

Where can I buy EVS20H3MW60?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What protection functions does the EVS Trip System6.0 provide?

Overload (long-time), instantaneous short-circuit, short-time short-circuit, and earth-fault protection.

MPN
EVS20H3MW60