Skip to main content
Schneider Electric EVS32H3MW60 — Air Circuit Breakers

Schneider Electric EVS32H3MW60 EasyPact EVS Circuit Breaker,

MPNEVS32H3MW60
Active

Schneider Electric EasyPact EVS, circuit breaker, EVS32H3MW60, 3P, 3200 A, 65 kA Icu at 440 V AC, drawout, electronic trip unit EVS Trip System6.0.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EVS32H3MW60 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact EVS
ApplicationDistribution
EVS32H3MW60 — Electrical ratings
ParameterValue
Rated current (In)3200 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
EVS32H3MW60 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
EVS32H3MW60 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
EVS32H3MW60 — Mechanical & connection
ParameterValue
Control typeManually operated
Mounting modeDrawout
Mounting supportRail Base plate
Contact position indicatorYes
Width441 mm
Height439 mm
Depth395 mm
Connection pitch115 mm without spreader
Connection locationRear
EVS32H3MW60 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1
EVS32H3MW60 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric EVS32H3MW60 is an EasyPact EVS drawout circuit breaker rated 3200 A at 40 °C with a 65 kA Icu breaking capacity at 220–440 V AC. The electronic EVS Trip System6.0 gives you four protection curves: overload (long-time), instantaneous short-circuit, short-time short-circuit, and earth fault. For a distribution board feeding a 3200 A bus, this is the main breaker that sets the fault withstand for everything behind it.

Drawout mounting and panel integration

This breaker is drawout type — the moving portion slides out of a fixed cradle for safe inspection or swap without disturbing the bus connections. It mounts on a rail or base plate and takes rear vertical or horizontal connections. The 115 mm connection pitch without spreader tells you the busbar centers. At 441 mm wide × 439 mm high × 395 mm deep, it fills a standard switchgear cubicle; the IP40 enclosure keeps out tools and fingers but isn't sealed against washdown — this lives in a dry indoor MV/LV room.

Frequently asked questions

Where can I buy EVS32H3MW60 and how do I get a price?

The EVS32H3MW60 is sourced and quoted to order against an RFQ through independent distribution. Submit a request for current pricing and availability — confirmed at quote time.

What is EVS32H3MW60's listed depth?

The EVS32H3MW60 has a depth of 395 mm.

What compliance documentation does this brand provide for EVS32H3MW60?

The EVS32H3MW60 is designed to IEC 60947-2 with a rated insulation voltage of 1000 V AC and pollution degree 4 per IEC 60664-1. It is suitable for isolation per IEC 60947-2.

MPN