Skip to main content
Schneider Electric EVS40H3MF20 — Air Circuit Breakers

Schneider Electric EVS40H3MF20 EasyPact EVS40H Circuit Break

MPNEVS40H3MF20
Active

Schneider Electric EasyPact EVS, EVS40H3MF20, circuit breaker, 4000 A rated current at 40 °C, 65 kA Icu at 440 V AC, 3-pole, electronically controlled.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EVS40H3MF20 — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact EVS
ApplicationDistribution
EVS40H3MF20 — Electrical ratings
ParameterValue
Rated current (In)4000 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
EVS40H3MF20 — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
EVS40H3MF20 — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
EVS40H3MF20 — Mechanical & connection
ParameterValue
Control typeManually operated
Mounting modeFixed
Mounting supportRail Base plate
Contact position indicatorYes
Width422 mm
Height352 mm
Depth297 mm
Connection pitch115 mm without spreader
Connection locationRear
EVS40H3MF20 — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1
EVS40H3MF20 — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The Schneider Electric EVS40H3MF20 is a fixed-mount, manually operated 3-pole air circuit breaker from the EasyPact EVS series. It carries a 4000 A rated current at 40 °C and is built to IEC 60947-2 as a Category B device — meaning it's designed for distribution duty where selectivity with downstream breakers matters, not just motor starting. The 65 kA Icu at 220...440 V AC and 50 kA at 690 V AC give it headroom for high-fault industrial service; that 65 kA figure at the common 400 V level is the one that'll matter for most plant main or feeder applications.

The EVS Trip System2.0 is an electronic trip unit rated at 4000 A CT. It provides overload protection with a long-time curve and instantaneous short-circuit protection.

Frequently asked questions

What are the key ratings of the EVS40H3MF20?

Rated current is 4000 A at 40 °C. Breaking capacity is 65 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2. It's a 3-pole, Category B breaker with an electronic EVS Trip System2.0 trip unit.

Where can I buy the EVS40H3MF20 and how is it quoted?

This part is sourced through independent distribution and quoted to order against an RFQ. Availability and current pricing are confirmed at the time of quote — submit an RFQ for your volume and delivery requirements.

What compliance documentation does Schneider Electric provide for the EVS40H3MF20?

The breaker is certified to IEC 60947-2 and carries an IP40 degree of protection. It is suitable for isolation per that standard. Specific RoHS, REACH, or UL documentation should be requested at quote time as part of the compliance package.

MPN
EVS40H3MF20