Skip to main content
Schneider Electric EVS40H3NW5A — Air Circuit Breakers

EVS40H3NW5A EasyPact EVS 4000A Circuit Breaker, 65kA

MPNEVS40H3NW5A
Active

Schneider Electric EasyPact EVS, EVS40H3NW5A, 4000 A drawout circuit breaker, 3P, 65 kA Icu at 440 V AC, electronic trip unit EVS Trip System5A, IEC 60947-2.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EVS40H3NW5A — Identification
ParameterValue
Product typeCircuit breaker
RangeEasyPact
Product rangeEasyPact EVS
ApplicationDistribution
EVS40H3NW5A — Electrical ratings
ParameterValue
Rated current (In)4000 A at 40 °C
Rated operational voltage (Ue)690 V AC 50/60 Hz conforming to IEC 60947-2
Poles3P
Rated insulation voltage (Ui)1000 V AC 50/60 Hz conforming to IEC 60947-2
Rated impulse withstand voltage (Uimp)12 kV conforming to IEC 60947-2
Network typeAC
Network frequency50/60 Hz
Suitable for isolationYes conforming to IEC 60947-2
EVS40H3NW5A — Breaking & withstand capacity
ParameterValue
Rated service breaking capacity (Ics)65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-time withstand current (Icw)65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2
Rated short-circuit making capacity (Icm)143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity codeH
EVS40H3NW5A — Performance
ParameterValue
Breaking time, max.25 ms
Closing response time, max.70 ms
Mechanical durability (cycles)20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
Electrical durability (cycles)Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2
Utilisation categoryCategory B
EVS40H3NW5A — Mechanical & connection
ParameterValue
Control typeElectrically operated
Mounting modeDrawout
Mounting supportRail Base plate
Contact position indicatorYes
Width441 mm
Height439 mm
Depth395 mm
Connection pitch115 mm without spreader
Connection locationRear
EVS40H3NW5A — Environmental
ParameterValue
Operating ambient temperature-5...70 °C
Storage ambient temperature-40...85 °C without control unit -25...85 °C with control unit
IP degree of protectionIP40
Pollution degree4 conforming to IEC 60664-1
EVS40H3NW5A — Approvals
ParameterValue
StandardsIEC 60947-2

Product details

The EVS40H3NW5A is a 4000 A rated, 3-pole drawout circuit breaker from Schneider Electric's EasyPact EVS range, designed for distribution applications per IEC 60947-2. At 690 V AC the breaking capacity is 50 kA Icu, still substantial for industrial mains. The electronic trip unit (EVS Trip System5A) provides overload protection with long-time delay, short-time short-circuit protection, and instantaneous short-circuit protection. The 20-minute thermal memory before and after tripping means the breaker remembers prior heating events — important for motor or transformer feeders where repeated overloads can accumulate thermal stress. Drawout mounting (with rail and base plate support) allows the breaker to be racked out for maintenance without disturbing the bus connections — standard for large switchgear where downtime for breaker swap must be minutes, not hours. Rear connection, vertical or horizontal orientation, and a 115 mm connection pitch without spreader define the busbar layout.

The part carries IEC 60947-2 certification for circuit-breaker performance, isolation suitability (yes, per standard), and Category B utilization — meaning it is designed for high-fault-level distribution without specific backup protection. Pollution degree 4 per IEC 60664-1 confirms it is rated for harsh industrial environments with conductive pollution.

The digital display provides fault indication for internal fault, overload, and short-circuit events — useful for field service techs to read the last trip cause without external software. The contact position indicator confirms open/closed state mechanically. Electrical durability is rated at 5000 cycles at 440/690 V AC without maintenance per IEC 60947-2. Mechanical durability is 20000 cycles with maintenance, 10000 without. Maximum breaking time is 25 ms — fast enough to limit let-through energy for downstream components.

Frequently asked questions

Where can I buy EVS40H3NW5A and how do I get a price?

The EVS40H3NW5A is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm price and lead time.

What is the closest alternative to EVS40H3NW5A in the EasyPact EVS family?

Within the EasyPact EVS range, the closest alternative would be a different breaking-capacity code (H vs S vs L) or a different trip-unit rating. The EVS40H3NW5A is the 4000 A, H breaking capacity variant. No pin-compatible direct drop-in exists without verifying the cradle and busbar interface.

What is EVS40H3NW5A's listed depth?

The EVS40H3NW5A has a depth of 395 mm.

What is EVS40H3NW5A's listed range?

The EVS40H3NW5A belongs to the Schneider Electric EasyPact EVS range.

What compliance documentation does this brand provide for EVS40H3NW5A?

The EVS40H3NW5A is certified to IEC 60947-2 and is suitable for isolation per that standard. It carries pollution degree 4 per IEC 60664-1. Specific RoHS, REACH, or UL documentation should be requested at quote time as the evidence does not list those marks.

MPN