The Schneider Electric EVS40H4MW5A is a 4-pole drawout circuit breaker from the EasyPact EVS range, rated 4000 A at 40 °C with a trip unit rating of 4000 A. Its breaking capacity is 65 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2 — meaning it can safely interrupt fault currents up to those levels without upstream cascading. Rated for Category B utilization (IEC 60947-2), it delivers 5000 electrical cycles without maintenance at 440/690 V AC, and 10000 mechanical cycles without maintenance (20000 with maintenance).
Schneider Electric EVS40H4MW5A EasyPact EVS Circuit Breaker,
MPNEVS40H4MW5A
Active
Schneider Electric EasyPact EVS, EVS40H4MW5A, 4-pole drawout circuit breaker, 4000 A rated current, 65 kA Icu at 440 V AC, IEC 60947-2.
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Product type | Circuit breaker |
| Range | EasyPact |
| Product range | EasyPact EVS |
| Application | Distribution |
| Parameter | Value |
|---|---|
| Rated current (In) | 4000 A at 40 °C |
| Rated operational voltage (Ue) | 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Poles | 4P |
| Rated insulation voltage (Ui) | 1000 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated impulse withstand voltage (Uimp) | 12 kV conforming to IEC 60947-2 |
| Network type | AC |
| Network frequency | 50/60 Hz |
| Suitable for isolation | Yes conforming to IEC 60947-2 |
| Parameter | Value |
|---|---|
| Rated service breaking capacity (Ics) | 65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated short-time withstand current (Icw) | 65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Rated short-circuit making capacity (Icm) | 143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity | 65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2 |
| Breaking capacity code | H |
| Parameter | Value |
|---|---|
| Breaking time, max. | 25 ms |
| Closing response time, max. | 70 ms |
| Mechanical durability (cycles) | 20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2 |
| Electrical durability (cycles) | Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 |
| Utilisation category | Category B |
| Parameter | Value |
|---|---|
| Control type | Manually operated |
| Mounting mode | Drawout |
| Mounting support | Rail Base plate |
| Contact position indicator | Yes |
| Width | 441 mm |
| Height | 439 mm |
| Depth | 395 mm |
| Connection pitch | 115 mm without spreader |
| Connection location | Rear |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -5...70 °C |
| Storage ambient temperature | -40...85 °C without control unit -25...85 °C with control unit |
| IP degree of protection | IP40 |
| Pollution degree | 4 conforming to IEC 60664-1 |
| Parameter | Value |
|---|---|
| Standards | IEC 60947-2 |
Product details
Frequently asked questions
Where can I buy EVS40H4MW5A and get a price?
This part is sourced to order against an RFQ through independent distribution. Submit a request for current pricing and availability — confirmed at quote time.
What is the breaking capacity of EVS40H4MW5A?
65 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2.
What compliance standards does EVS40H4MW5A meet?
It is designed to IEC 60947-2 for circuit breakers, with suitability for isolation confirmed per that standard. Pollution degree 4 per IEC 60664-1.
MPN
EVS40H4MW5A