Skip to main content
Schneider Electric EVS40H4NW5A

Schneider Electric EVS40H4NW5A EasyPact EVS 4000A Circuit Br

MPN EVS40H4NW5A
Active

Schneider Electric EasyPact EVS, EVS40H4NW5A, 4-pole drawout circuit breaker, 4000 A rated current, 65 kA Icu at 440 V AC, electronic trip unit.

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EVS40H4NW5A key specifications
ParameterValue
Control typeElectrically operated
Display typeDigital display
Trip unit typeElectronic
Main product or component typeCircuit breaker
Voltage690 V AC 50/60 Hz conforming to IEC 60947-2
Insulation voltage ui1000 V AC 50/60 Hz conforming to IEC 60947-2
Breaking capacity65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
Utilization categoryCategory B
IP ratingIP40
Terminal pitch115 mm without spreader
Temp storage max85 °C
Temp storage min-40 °C

All specifications

EVS40H4NW5A additional specifications
ParameterValue
Temp operating max70 °C
Temp operating min-5 °C
Pollution degree4 conforming to IEC 60664-1
Depth395 mm
Width441 mm
Height439 mm
Mechanical life cycles20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2
ApplicationDistribution
Operating temperature-5...70 °C

Product details

The Schneider Electric EVS40H4NW5A is a 4-pole drawout air circuit breaker from the EasyPact EVS family, rated 4000 A at 40 °C and built to IEC 60947-2 for distribution duty. That 4000 A continuous rating means it handles the main incoming feed for a large industrial switchboard or a high-current bus riser — not a feeder breaker for a motor control center. The drawout cradle lets you rack the breaker out for maintenance without unbolting power cables, which cuts downtime when you're swapping a trip unit or doing a megger test on the bus.

Rated 65 kA Icu at 220…440 V AC and 50 kA Icu at 690 V AC per IEC 60947-2. The 25 ms maximum breaking time means the arc is quenched inside two cycles at 50 Hz, which limits the let-through energy on downstream gear.

Trip unit and protection logic

Fitted with the EVS Trip System5A electronic trip unit, rated 4000 A. It provides overload (long-time), short-time, and instantaneous short-circuit protection — that's the full curve set you need for selective coordination on a distribution main. The 20-minute thermal memory before and after tripping means the breaker remembers prior heating events, so it doesn't reclose into a still-hot conductor and nuisance-trip again. That matters on a line where a momentary overload from a large motor start could otherwise cause a lockout.

Certified to IEC 60947-2, suitability for isolation marked on the device. Electrical durability: 5000 cycles at 440/690 V without maintenance per Category B. Mechanical durability: 20,000 cycles with maintenance, 10,000 without. That's a solid service life for a main breaker that cycles maybe a few dozen times a year.

MPN
EVS40H4NW5A