Schneider Electric EZ9F26106 — 1-Pole MCB (DIN Rail)

Schneider Electric EZ9F26106 Easy9 MCB, 1P, B Curve, 6 A, 6

MPNEZ9F26106
Obsolete

Schneider Electric Easy9 MCB, EZ9F26106, 1P, B curve, 6 A, 6 kA breaking capacity at 230 V AC, thermal-magnetic trip, DIN rail clip-on.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZ9F26106 — Identification
ParameterValue
Product / component typeMiniature circuit-breaker
Product rangeEasy9
Device short nameEasy9 MCB
Number of protected poles1
Device applicationDistribution
EZ9F26106 — Electrical & Protection
ParameterValue
Rated current (In)6 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu / AIR)6000 A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)10000 cycles
EZ9F26106 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Mounting modeClip-on
Width18 mm
Height81 mm
Depth66.5 mm
Tightening torque (by circuit)2 N.m top or bottom
EZ9F26106 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
EZ9F26106 — Approvals
ParameterValue
Conformity standardsIEC 60898-1
EZ9F26106 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60898-1
[Uimp] rated impulse withstand voltage4 kV conforming to IEC 60898-1

Product details

It is designed for distribution in residential and light commercial AC networks at 230 V, 50/60 Hz. The B curve means the magnetic trip activates at 3 to 5 times the rated current (18 to 30 A for this 6 A unit), making it a good fit for resistive and general-purpose loads where inrush is moderate — lighting circuits, socket outlets, small appliances. Breaking capacity is 6 kA (Icn and Ics at 230 V AC), certified to IEC 60898-1. That is the standard fault-clearing rating for final subcircuits in most domestic and light commercial panels — it will safely interrupt a short-circuit up to 6,000 A without welding the contacts or damaging the enclosure.

Frequently asked questions

What is the breaking capacity of the EZ9F26106?

6 kA Icn and Ics at 230 V AC, 50/60 Hz, certified to IEC 60898-1. That is the standard fault rating for final subcircuits in residential and light commercial distribution boards.

What is the closest alternative to the EZ9F26106 in the same family?

Within the Easy9 range, the closest sibling is the same 1P, B-curve, 6 A MCB with the same 6 kA breaking capacity and DIN-rail footprint. The difference is negligible for fit — the EZ9F26106 is the standard order code for this rating.

What compliance documentation does Schneider provide for the EZ9F26106?

The MCB is certified to IEC 60898-1. The Easy9 range typically carries CE marking for the European market. Specific RoHS and REACH declarations are available from Schneider Electric's documentation portal for this order code.