It is designed for distribution in residential and light commercial AC networks at 230 V, 50/60 Hz. The B curve means the magnetic trip activates at 3 to 5 times the rated current (18 to 30 A for this 6 A unit), making it a good fit for resistive and general-purpose loads where inrush is moderate — lighting circuits, socket outlets, small appliances. Breaking capacity is 6 kA (Icn and Ics at 230 V AC), certified to IEC 60898-1. That is the standard fault-clearing rating for final subcircuits in most domestic and light commercial panels — it will safely interrupt a short-circuit up to 6,000 A without welding the contacts or damaging the enclosure.
Schneider Electric EZ9F26106 Easy9 MCB, 1P, B Curve, 6 A, 6
Schneider Electric Easy9 MCB, EZ9F26106, 1P, B curve, 6 A, 6 kA breaking capacity at 230 V AC, thermal-magnetic trip, DIN rail clip-on.
Specifications
| Parameter | Value |
|---|---|
| Product / component type | Miniature circuit-breaker |
| Product range | Easy9 |
| Device short name | Easy9 MCB |
| Number of protected poles | 1 |
| Device application | Distribution |
| Parameter | Value |
|---|---|
| Rated current (In) | 6 A |
| Rated operational voltage (Ue) | 230 V AC 50/60 Hz |
| Tripping curve code | B |
| Magnetic tripping limit | 3...5 x In |
| Breaking capacity (Icu / AIR) | 6000 A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1 |
| Network type (AC/DC) | AC |
| Network frequency | 50/60 Hz |
| Trip unit technology | Thermal-magnetic |
| Control / actuation type | Toggle |
| Mechanical durability (cycles) | 10000 cycles |
| Parameter | Value |
|---|---|
| Terminal connections / wire range | Tunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible |
| Mounting support | DIN rail |
| Mounting mode | Clip-on |
| Width | 18 mm |
| Height | 81 mm |
| Depth | 66.5 mm |
| Tightening torque (by circuit) | 2 N.m top or bottom |
| Parameter | Value |
|---|---|
| Operating ambient temperature | -5...60 °C |
| Storage ambient temperature | -40...85 °C |
| IP degree of protection | IP20 conforming to IEC 60529 |
| Parameter | Value |
|---|---|
| Conformity standards | IEC 60898-1 |
| Parameter | Value |
|---|---|
| [Ui] rated insulation voltage | 500 V AC 50/60 Hz conforming to IEC 60898-1 |
| [Uimp] rated impulse withstand voltage | 4 kV conforming to IEC 60898-1 |
Product details
Frequently asked questions
What is the breaking capacity of the EZ9F26106?
6 kA Icn and Ics at 230 V AC, 50/60 Hz, certified to IEC 60898-1. That is the standard fault rating for final subcircuits in residential and light commercial distribution boards.
What is the closest alternative to the EZ9F26106 in the same family?
Within the Easy9 range, the closest sibling is the same 1P, B-curve, 6 A MCB with the same 6 kA breaking capacity and DIN-rail footprint. The difference is negligible for fit — the EZ9F26106 is the standard order code for this rating.
What compliance documentation does Schneider provide for the EZ9F26106?
The MCB is certified to IEC 60898-1. The Easy9 range typically carries CE marking for the European market. Specific RoHS and REACH declarations are available from Schneider Electric's documentation portal for this order code.