Skip to main content
Schneider Electric EZ9F26116 — 1-Pole MCB (DIN Rail)

Schneider Electric EZ9F26116 Easy9 MCB, 1P 16A B-Curve, 6kA

MPNEZ9F26116
Obsolete

Schneider Electric Easy9 MCB, 1-pole 16 A, B-curve, 6 kA breaking capacity at 230 V AC, IEC 60898-1, DIN-rail clip-on, grey (RAL 7035), 18 mm width.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZ9F26116 — Identification
ParameterValue
Product / component typeMiniature circuit-breaker
Product rangeEasy9
Device short nameEasy9 MCB
Number of protected poles1
Device applicationDistribution
EZ9F26116 — Electrical & Protection
ParameterValue
Rated current (In)16 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu / AIR)6000 A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)10000 cycles
EZ9F26116 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Mounting modeClip-on
Width18 mm
Height81 mm
Depth66.5 mm
Tightening torque (by circuit)2 N.m top or bottom
EZ9F26116 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
EZ9F26116 — Approvals
ParameterValue
Conformity standardsIEC 60898-1
EZ9F26116 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60898-1
[Uimp] rated impulse withstand voltage4 kV conforming to IEC 60898-1

Product details

The Schneider Electric EZ9F26116 is a 1-pole miniature circuit breaker from the Easy9 range, rated 16 A with a B-curve trip characteristic. It breaks 6 kA at 230 V AC per IEC 60898-1, making it a standard choice for residential and light commercial distribution boards protecting lighting and socket-outlet circuits.

Clip-on mounting to DIN rail (35 mm) — the 18 mm width occupies 2 module pitches. Tunnel terminals accept 1–25 mm² rigid or 1–16 mm² flexible cable; torque to 2 N·m. IP20 finger-safe front, suitable for enclosed distribution boards.

Marked as current production (active lifecycle).

Frequently asked questions

What is the breaking capacity of EZ9F26116?

6 kA Icn and 6 kA Ics (100% of Icn) at 230 V AC, 50/60 Hz, per IEC 60898-1.

What compliance standards does EZ9F26116 meet?

Designed to IEC 60898-1; rated insulation voltage 500 V AC, impulse withstand 4 kV. IP20 per IEC 60529. Suitable for isolation per the standard.

Where can I buy EZ9F26116 and how is it quoted?

Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing confirmed at quote time.

MPN
EZ9F26116