Skip to main content
Schneider Electric EZ9F26132 — 1-Pole MCB (DIN Rail)

Schneider Electric EZ9F26132 Easy9 MCB, 1P, B Curve, 32 A, 6

MPNEZ9F26132
Obsolete

Schneider Electric Easy9 MCB, EZ9F26132, 1P, B curve, 32 A, 6 kA breaking capacity at 230 V AC, IEC 60898-1, thermal-magnetic, clip-on DIN rail.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZ9F26132 — Identification
ParameterValue
Product / component typeMiniature circuit-breaker
Product rangeEasy9
Device short nameEasy9 MCB
Number of protected poles1
Device applicationDistribution
EZ9F26132 — Electrical & Protection
ParameterValue
Rated current (In)32 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Tripping curve codeB
Magnetic tripping limit3...5 x In
Breaking capacity (Icu / AIR)6000 A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)10000 cycles
EZ9F26132 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminal (top or bottom) 1...25 mm² flexible Tunnel type terminal (top or bottom) 1...35 mm² rigid
Mounting supportDIN rail
Mounting modeClip-on
Width18 mm
Height81 mm
Depth66.5 mm
Tightening torque (by circuit)3.5 N.m top or bottom
EZ9F26132 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
EZ9F26132 — Approvals
ParameterValue
Conformity standardsIEC 60898-1
EZ9F26132 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60898-1
[Uimp] rated impulse withstand voltage4 kV conforming to IEC 60898-1

Product details

The EZ9F26132 is a 1-pole miniature circuit breaker from Schneider Electric's Easy9 range, rated 32 A with a B tripping curve. The B curve means the magnetic trip operates at 3 to 5 times In (96–160 A instantaneously), which is the standard choice for resistive and general-purpose loads in residential or light commercial distribution boards — not for motor starting where higher inrush would nuisance-trip a B curve. The 6 kA breaking capacity (Icn and Ics both 6 kA at 230 V AC) tells you it can safely interrupt a fault current up to 6,000 A without welding contacts or cascading damage upstream; that's adequate for most final subcircuits in a TN or TT system where the prospective short-circuit current stays under 6 kA. The 500 V rated insulation voltage (Ui) and 4 kV impulse withstand (Uimp) confirm it's isolated for use in 230/400 V networks per IEC 60898-1.

Deployment context

Clip-on mounting to a 35 mm DIN rail, 18 mm width (1 module), so it slots into a standard distribution board or sub-panel alongside other Easy9 devices. Tunnel terminals accept up to 35 mm² rigid or 25 mm² flexible cable; tightening torque is 3.5 N·m.

Frequently asked questions

Where can I buy EZ9F26132 and how do I get a price?

The EZ9F26132 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time.

What is the closest pin-compatible alternative to EZ9F26132 in this component family?

Within the Easy9 range, the closest alternative would be a different current rating or curve code (e.g., C curve for motor circuits) — same 1P footprint, same breaking capacity, same DIN-rail clip. The B-curve 32 A version is the standard choice for resistive loads; if your circuit sees motor inrush, step to a C-curve variant.

What is EZ9F26132's listed depth (66.5 mm) on this component line?

The EZ9F26132 has a depth of 66.5 mm, which is standard for the Easy9 1P MCB form factor.

What is EZ9F26132's listed poles (1P) on this component line?

The EZ9F26132 is a 1-pole (1P) miniature circuit breaker, protecting one phase.

What compliance documentation does this brand provide for EZ9F26132 (RoHS, REACH, UL, IEC)?

The EZ9F26132 is designed and certified to IEC 60898-1. It carries a suitability-for-isolation marking per that standard. For RoHS/REACH declarations and any UL listing, refer to the Schneider Electric product compliance portal using the order code.

MPN