Skip to main content
Schneider Electric EZ9F34102 — 1-Pole MCB (DIN Rail)

Schneider Electric EZ9F34102 Easy9 MCB, 1P C-Curve 2A, 4.5kA

MPNEZ9F34102
Obsolete

Schneider Electric Easy9 MCB, 1P, 2 A, C-curve, 4.5 kA breaking capacity at 230 V AC, IEC 60898-1, clip-on DIN rail mount, grey (RAL 7035).

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZ9F34102 — Identification
ParameterValue
Product / component typeMiniature circuit-breaker
Product rangeEasy9
Device short nameEasy9 MCB
Number of protected poles1
Device applicationDistribution
EZ9F34102 — Electrical & Protection
ParameterValue
Rated current (In)2 A
Rated operational voltage (Ue)230 V AC 50/60 Hz
Tripping curve codeC
Magnetic tripping limit5...10 x In
Breaking capacity (Icu / AIR)4500 A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1 4500 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1
Network type (AC/DC)AC
Network frequency50/60 Hz
Trip unit technologyThermal-magnetic
Control / actuation typeToggle
Mechanical durability (cycles)10000 cycles
EZ9F34102 — Mounting & Connection
ParameterValue
Terminal connections / wire rangeTunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...16 mm² flexible
Mounting supportDIN rail
Mounting modeClip-on
Width18 mm
Height81 mm
Depth66.5 mm
Tightening torque (by circuit)2 N.m top or bottom
EZ9F34102 — Environmental
ParameterValue
Operating ambient temperature-5...60 °C
Storage ambient temperature-40...85 °C
IP degree of protectionIP20 conforming to IEC 60529
EZ9F34102 — Approvals
ParameterValue
Conformity standardsIEC 60898-1
EZ9F34102 — Electrical
ParameterValue
[Ui] rated insulation voltage500 V AC 50/60 Hz conforming to IEC 60898-1
[Uimp] rated impulse withstand voltage4 kV conforming to IEC 60898-1

Product details

Rated breaking capacity (Icn) is 4500 A at both 230 V and 400 V AC, 50/60 Hz, per IEC 60898-1.

Width is 18 mm (one modular pitch), depth 66.5 mm, height 81 mm. Clip-on mounting to DIN rail. Tunnel terminals accept 1–25 mm² rigid or 1–16 mm² flexible; tighten to 2 N·m. IP20 finger-safe terminals — fine inside an enclosure, not for wet locations. Pollution degree 2 covers normal indoor environments with non-conductive contamination.

Designed and tested to IEC 60898-1. Rated insulation voltage 500 V AC, rated impulse withstand voltage 4 kV. Tropicalisation class 2 means it's treated for humidity up to 95% RH at 60 °C. Storage range -40 to 85 °C, operating range -5 to 60 °C.

Frequently asked questions

Where can I buy EZ9F34102 and get a price?

The EZ9F34102 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time.

What is the breaking capacity of EZ9F34102?

The rated breaking capacity (Icn) is 4500 A at both 230 V and 400 V AC, 50/60 Hz, per IEC 60898-1. The service breaking capacity (Ics) is the same 4.5 kA at 100% of Icn.

What is the depth of EZ9F34102?

The depth is 66.5 mm.

What compliance documentation does Schneider provide for EZ9F34102?

The breaker is designed to IEC 60898-1. It carries a rated impulse withstand voltage of 4 kV and is suitable for isolation per the standard.

MPN