Skip to main content
Schneider Electric EZ9F34210

Schneider Electric EZ9F34210 Easy9 MCB, 10 A, 2P, C-Curve, 4

MPN EZ9F34210
Active

Schneider Electric Easy9 series, EZ9F34210, miniature circuit breaker (MCB), 2-pole, 10 A rated current, C-curve, 4.5 kA breaking capacity per IEC 60898-1, DIN-rail mount, grey (RAL 7035).

Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZ9F34210 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage400 V AC 50 Hz
Insulation voltage ui500 V AC 50/60 Hz conforming to IEC 60898-1
Breaking capacity4500 A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1 4500 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1
Poles2P
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-25 °C

All specifications

EZ9F34210 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree2
ColorGrey (RAL 7035)
Depth66.5 mm
Width36 mm
Height81 mm
Electrical life cycles4000 cycles
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-25...60 °C

Product details

Breaking capacity is 4.5 kA at both 230 V and 400 V AC, conforming to IEC 60898-1. The rated service breaking capacity (Ics) is 100 % of Icn at 230 V, so the breaker can reclose after clearing a fault at its full rating without derating.

Fit and installation

Width is 36 mm (4 modules of 9 mm pitch), depth 66.5 mm, height 81 mm. The grey (RAL 7035) housing blends into a standard panel layout. IP20 finger-safe protection on the front face; suitable for dry indoor enclosures. Insulation voltage is 500 V AC. Impulse withstand voltage is 4 kV, which covers standard surge environments in distribution boards (pollution degree 2).

Durability and environmental range

Rated for 4,000 electrical cycles and 10,000 mechanical cycles. Tropicalisation treatment (class 2) and 95 % relative humidity tolerance suit warm, humid climates. Thermal-magnetic trip unit provides overload and short-circuit protection.

MPN