Breaking capacity is 4.5 kA at both 230 V and 400 V AC, conforming to IEC 60898-1. The rated service breaking capacity (Ics) is 100 % of Icn at 230 V, so the breaker can reclose after clearing a fault at its full rating without derating.
Fit and installation
Width is 36 mm (4 modules of 9 mm pitch), depth 66.5 mm, height 81 mm. The grey (RAL 7035) housing blends into a standard panel layout. IP20 finger-safe protection on the front face; suitable for dry indoor enclosures. Insulation voltage is 500 V AC. Impulse withstand voltage is 4 kV, which covers standard surge environments in distribution boards (pollution degree 2).
Durability and environmental range
Rated for 4,000 electrical cycles and 10,000 mechanical cycles. Tropicalisation treatment (class 2) and 95 % relative humidity tolerance suit warm, humid climates. Thermal-magnetic trip unit provides overload and short-circuit protection.