The 16 A rated current (In) and C-curve (magnetic trip 5–10 × In) mean this breaker handles general-purpose loads like lighting and socket circuits where inrush is moderate — it will not nuisance-trip on a motor start but clears a short fast enough for branch protection. The 4.5 kA breaking capacity at 230 V AC (Icn) and 4.5 kA service capacity (Ics at 100 % Icn) tell you it safely interrupts faults up to that level without needing an upstream current-limiting device in most residential panels. Rated insulation voltage is 500 V AC, operational voltage 400 V AC 50 Hz — it covers single-phase and line-to-line loads in a 230/400 V system.
Clip-on mounting to DIN rail (EN 60715). Width is 36 mm (4 module pitches at 9 mm). Depth 66.5 mm, height 81 mm. Tunnel terminals accept 1–25 mm² rigid or 1–16 mm² flexible cable; tightening torque 2 N·m. IP20 finger-safe front. Pollution degree 2, tropicalisation class 2 — suitable for dry indoor enclosures without condensation control.