The EZ9F34332 carries a 4.5 kA Icn at both 230 V and 400 V AC, conforming to IEC 60898-1. The service breaking capacity Ics equals Icn at 100 % — meaning after clearing a fault at its full rating the breaker remains functional and can be reclosed. For a panel builder, that simplifies coordination: you can place this MCB downstream of a higher-rated upstream device (e.g., a 10 kA MCCB) and the selectivity break is clean at the 4.5 kA threshold.
Thermal-magnetic trip and environmental range
The thermal-magnetic trip unit combines a bimetal element for overload protection and a solenoid for short-circuit. The C-curve magnetic trip is set at 5 to 10 times In, so a 32 A breaker trips instantaneously between 160 A and 320 A. Operating ambient temperature spans -25 to 60 °C with 95 % relative humidity; storage range is -40 to 85 °C. The IP20 finger-safe terminals accept up to 35 mm² rigid or 25 mm² flexible conductors, torqued to 3.5 N·m.