Skip to main content
Schneider Electric EZ9F34332 — Circuit Breaker Accessories

Schneider Electric EZ9F34332 Easy9 MCB, 32 A, 3P, C-Curve, 4

MPNEZ9F34332
Active

Schneider Electric Easy9 range, EZ9F34332 miniature circuit-breaker, 3P, 32 A, C-curve, 4.5 kA breaking capacity at 400 V AC, IEC 60898-1.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZ9F34332 — Identification
ParameterValue
Product / component typeMiniature circuit-breaker
Product rangeEasy9
Device applicationDistribution
EZ9F34332 — Electrical
ParameterValue
Network type (AC/DC)AC
Rated current [In]32 A
Rated operational voltage [Ue]400 V AC 50 Hz
Rated insulation voltage [Ui]500 V AC 50/60 Hz conforming to IEC 60898-1
Rated impulse withstand voltage [Uimp]4 kV conforming to IEC 60898-1
Network frequency50 Hz
Magnetic tripping limit5...10 x In
EZ9F34332 — Protection & Performance
ParameterValue
Breaking capacity4500 A Icn at 230 V AC 50/60 Hz conforming to IEC 60898-1 4500 A Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1
Rated service breaking capacity [Ics]4.5 kA 100 % x Icn at 400 V AC 50/60 Hz conforming to IEC 60898-1
Trip unit technologyThermal-magnetic
Suitability for isolationYes conforming to IEC 60898-1
Mechanical durability10000 cycles
Electrical durability4000 cycles
Local signallingWithout
Contact position indicatorYes
EZ9F34332 — Mechanical
ParameterValue
Connections / terminalsTunnel type terminal (top or bottom) 1...25 mm² flexible Tunnel type terminal (top or bottom) 1...35 mm² rigid
Device short nameEasy9 MCB
Control typeToggle
Mounting modeClip-on
Mounting supportDIN rail
Usable 9 mm pitches6
Width54 mm
Height81 mm
Depth66.5 mm
ColourGrey (RAL 7035)
EZ9F34332 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to IEC 60529
Pollution degree2
Operating ambient air temperature-25...60 °C
Storage ambient air temperature-40...85 °C
EZ9F34332 — Approvals
ParameterValue
StandardsIEC 60898-1
EZ9F34332 — Specifications
ParameterValue
Curve codeC
Number of protected poles3

Product details

The EZ9F34332 carries a 4.5 kA Icn at both 230 V and 400 V AC, conforming to IEC 60898-1. The service breaking capacity Ics equals Icn at 100 % — meaning after clearing a fault at its full rating the breaker remains functional and can be reclosed. For a panel builder, that simplifies coordination: you can place this MCB downstream of a higher-rated upstream device (e.g., a 10 kA MCCB) and the selectivity break is clean at the 4.5 kA threshold.

Thermal-magnetic trip and environmental range

The thermal-magnetic trip unit combines a bimetal element for overload protection and a solenoid for short-circuit. The C-curve magnetic trip is set at 5 to 10 times In, so a 32 A breaker trips instantaneously between 160 A and 320 A. Operating ambient temperature spans -25 to 60 °C with 95 % relative humidity; storage range is -40 to 85 °C. The IP20 finger-safe terminals accept up to 35 mm² rigid or 25 mm² flexible conductors, torqued to 3.5 N·m.

Frequently asked questions

What is the breaking capacity of EZ9F34332?

The EZ9F34332 has a rated breaking capacity Icn of 4500 A at both 230 V AC and 400 V AC, 50/60 Hz, conforming to IEC 60898-1. The service breaking capacity Ics is 4.5 kA at 100 % of Icn.

What is the closest alternative to EZ9F34332 in the Easy9 range?

Within the same Easy9 family, a higher-current variant like a 40 A 3P C-curve MCB would share the same DIN-rail footprint and terminal style, but the trip threshold and breaking capacity differ — verify coordination for your specific load before substituting.

What compliance documentation does Schneider provide for EZ9F34332?

The EZ9F34332 is certified to IEC 60898-1 and carries an impulse withstand voltage of 4 kV conforming to that standard. It is suitable for isolation per IEC 60898-1. For RoHS, REACH, and UL declarations, refer to the manufacturer's compliance documentation available on request.

MPN
EZ9F34332