Skip to main content
Schneider Electric EZ9F53206 — 2-Pole MCB (DIN Rail)

Schneider EZ9F53206 Easy9 MCB, 2-pole, 6 A, C-curve, 3 kA

MPNEZ9F53206
Obsolete

Schneider EZ9F53206 Mcb — now discontinued, supplied from remaining surplus and broker stock.

$8.05Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZ9F53206 — Identification
ParameterValue
Series / familyEasy9
Device short nameEasy9 MCB
Product / component typeMiniature circuit-breaker
Device applicationDistribution
EZ9F53206 — Electrical
ParameterValue
Rated current [In]6 A
Number of protected poles2
Rated operational voltage [Ue]400 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
EZ9F53206 — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit8.5 x In +/- 20 %
Breaking capacity (Icu)3 kA Icu at 400 V AC 50/60 Hz conforming to SANS 60947-2
Rated service breaking capacity [Ics]3 kA 100 % x Icu at 400 V AC 50/60 Hz conforming to SANS 60947-2
Energy limitation class3 conforming to SANS 60947-2
Suitable for isolationYes conforming to SANS 60947-2
Trip unit technologyThermal-magnetic
Operating / control typeToggle
Mechanical durability (cycles)10000 cycles
EZ9F53206 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth66.5 mm
Mounting supportDIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque2 N.m top or bottom
Local signalling / indicationWithout
Contact position indicatorYes
EZ9F53206 — Environmental
ParameterValue
Operating temperature range-5...60 °C
Storage temperature range-40...85 °C
Relative humidity95 % at -5...60 °C
EZ9F53206 — Approvals
ParameterValue
Standards / complianceSANS 60947-2

Product details

Overview

The EZ9F53206 is a Schneider Easy9 miniature circuit breaker rated 6 A, 2-pole, C-curve, with a 3 kA breaking capacity per SANS 60947-2.

Selection and sizing

The 6 A C-curve trips magnetically at 8.5 x In ±20 %, so it clears short-circuit faults on lighting and general-purpose distribution circuits without nuisance tripping on inrush.

MPN