Skip to main content
Schneider Electric EZ9F53216 — 2-Pole MCB (DIN Rail)

Schneider EZ9F53216 Easy9 MCB, 2-pole, 16 A, C-curve

MPNEZ9F53216
Obsolete

Schneider Electric Easy9 EZ9F53216 miniature circuit breaker, 2-pole, 16 A, C-curve, 3 kA breaking capacity (SANS 60947-2), 400 V AC, 60 Hz, thermal-magnetic trip, tunnel terminals 1…25 mm², grey (RAL 7035).

$8.05Ref. price · indicative, final on quote
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

EZ9F53216 — Identification
ParameterValue
Series / familyEasy9
Device short nameEasy9 MCB
Product / component typeMiniature circuit-breaker
Device applicationDistribution
EZ9F53216 — Electrical
ParameterValue
Rated current [In]16 A
Number of protected poles2
Rated operational voltage [Ue]400 V AC 50/60 Hz
Network type (AC/DC)AC
Network frequency50/60 Hz
EZ9F53216 — Protection
ParameterValue
Tripping curve codeC
Magnetic tripping limit8.5 x In +/- 20 %
Breaking capacity (Icu)3 kA Icu at 400 V AC 50/60 Hz conforming to SANS 60947-2
Rated service breaking capacity [Ics]3 kA 100 % x Icu at 400 V AC 50/60 Hz conforming to SANS 60947-2
Energy limitation class3 conforming to SANS 60947-2
Suitable for isolationYes conforming to SANS 60947-2
Trip unit technologyThermal-magnetic
Operating / control typeToggle
Mechanical durability (cycles)10000 cycles
EZ9F53216 — Mechanical
ParameterValue
9 mm pitches4
Width36 mm
Height81 mm
Depth66.5 mm
Mounting supportDIN rail
Mounting modeClip-on
Terminal connectionsTunnel type terminal (top or bottom) 1...25 mm² rigid Tunnel type terminal (top or bottom) 1...25 mm² flexible
Terminal tightening torque2 N.m top or bottom
Local signalling / indicationWithout
Contact position indicatorYes
EZ9F53216 — Environmental
ParameterValue
Operating temperature range-5...60 °C
Storage temperature range-40...85 °C
Relative humidity95 % at -5...60 °C
EZ9F53216 — Approvals
ParameterValue
Standards / complianceSANS 60947-2

Product details

Overview

The EZ9F53216 is a Schneider Easy9 miniature circuit breaker rated 16 A on a C-curve, switching a 2-pole 400 V AC distribution circuit with a 3 kA breaking capacity conforming to SANS 60947-2. Its thermal-magnetic trip unit triggers magnetically at 8.5 x In ±20 %, and the 4000 V impulse withstand and IP20 finger-safe terminals suit it for residential and light commercial panelboards.

At 16 A, the C-curve holds up to 5 x In for short-circuit coordination with downstream loads; the 3 kA Icu matches typical utility fault levels in South African distribution boards.

MPN
EZ9F53216