Skip to main content
Schneider Electric EZ9F53325

Schneider Electric EZ9F53325 Easy9 MCB, 25 A, 3P, C-Curve, 3

MPN EZ9F53325
Active

Schneider Electric Easy9 MCB, 25 A, 3P, C-curve, 3 kA Icu at 400 V AC, SANS 60947-2, thermal-magnetic trip, DIN rail clip-on, grey (RAL 7035).

$11.56 Ref. price · indicative, final on quote
Dispatch SLA24-48h Global Rush
Quality CheckOriginal Seal & Physical QC
IncotermsDAP / DDP Available
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & stockist· Listing updated Sep 2026

Specifications

EZ9F53325 key specifications
ParameterValue
Control typeToggle
Trip unit typeThermal-magnetic
Main product or component typeMiniature circuit-breaker
Voltage400 V AC 50/60 Hz
Insulation voltage ui500 V AC 50/60 Hz conforming to SANS 60947-2
Breaking capacity3 kA Icu at 400 V AC 50/60 Hz conforming to SANS 60947-2
Poles3P
IP ratingIP20
Temp storage max85 °C
Temp storage min-40 °C
Temp operating max60 °C
Temp operating min-5 °C

All specifications

EZ9F53325 additional specifications
ParameterValue
Storage temperature-40...85 °C
Pollution degree2
ColorGrey (RAL 7035)
Depth66.5 mm
Width54 mm
Height81 mm
Electrical life cycles4000 cycles
Mechanical life cycles10000 cycles
ApplicationDistribution
Operating temperature-5...60 °C

Product details

The Schneider Electric EZ9F53325 is an Easy9 miniature circuit-breaker rated at 25 A with 3 poles, C-curve, and a breaking capacity of 3 kA Icu at 400 V AC 50/60 Hz conforming to SANS 60947-2.

The 25 A rating and C-curve suit general-purpose distribution circuits — lighting, socket outlets, small motor loads — where the inrush is moderate. That matters for a panel where you want to restore service without swapping the device after a trip. Limitation class 3 per SANS 60947-2 means the breaker limits the let-through energy during a short-circuit, protecting downstream equipment. Pollution degree 2 is the standard for a clean indoor panel — no condensation or conductive dust expected. The IP20 finger-safe terminals are fine inside an enclosure; outside it, you'd need a separate enclosure.

Clip-on mount to DIN rail, 54 mm wide (6 x 9 mm pitches), 81 mm high, 66.5 mm deep. Tightening torque 2 N.m. The toggle control and contact position indicator give a clear visual of the state — useful during panel commissioning or troubleshooting.

MPN